⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

325 Amp Cable Size at 70 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 325 A over 70 m (229.7 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 1.22V (2.54%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 4.02V (8.37%)
Voltage at Load46.8 VLine Loss: 395.6 W
Max Power & Breaker15.6 kW350A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 325A at 70m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A649.13 V (1352.36%)0.0 V1070.77 V (2230.76%)210968.3 WDrop High
2.5 mm²24 A18 A389.48 V (811.42%)0.0 V642.46 V (1338.46%)126581.0 WDrop High
4 mm²32 A25 A243.43 V (507.14%)0.0 V401.54 V (836.54%)79113.1 WDrop High
6 mm²41 A32 A162.28 V (338.09%)0.0 V267.69 V (557.69%)52742.1 WDrop High
10 mm²57 A44 A97.37 V (202.85%)0.0 V160.62 V (334.61%)31645.2 WDrop High
16 mm²76 A59 A60.86 V (126.78%)0.0 V100.38 V (209.13%)19778.3 WDrop High
25 mm²101 A78 A38.95 V (81.14%)9.1 V64.25 V (133.85%)12658.1 WDrop High
35 mm²125 A97 A27.82 V (57.96%)20.2 V45.89 V (95.6%)9041.5 WDrop High
50 mm²151 A118 A19.47 V (40.57%)28.5 V32.12 V (66.92%)6329.1 WDrop High
70 mm²192 A150 A13.91 V (28.98%)34.1 V22.95 V (47.8%)4520.8 WDrop High
95 mm²232 A181 A10.25 V (21.35%)37.8 V16.91 V (35.22%)3331.1 WDrop High
120 mm²269 A210 A8.11 V (16.9%)39.9 V13.38 V (27.88%)2637.1 WDrop High
150 mm²309 A241 A6.49 V (13.52%)41.5 V10.71 V (22.31%)2109.7 WDrop High
185 mm²353 A275 A5.26 V (10.97%)42.7 V8.68 V (18.09%)1710.6 WDrop High
240 mm²415 A324 A4.06 V (8.45%)43.9 V6.69 V (13.94%)1318.6 WDrop High
300 mm²477 A372 A3.25 V (6.76%)44.8 V5.35 V (11.15%)1054.8 WDrop High
400 mm²570 A445 A2.43 V (5.07%)45.6 V4.02 V (8.37%)791.1 WDrop High

FAQ — 325 Amp Cable Size at 70 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 325A at 70 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 325A over 70m at 48V (voltage drop: 1.22V or 2.54%).

What is the power capacity of 325A at 48V?

At unity power factor, 325A at 48V supports 15.6 kW with a standard 350A circuit breaker.