325 Amp Cable Size at 25 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 325 A over 25 m (82.0 ft).

Copper Cable (≤3% Drop)300 mm²Drop: 1.16V (2.41%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 1.43V (2.99%)
Voltage at Load46.8 VLine Loss: 376.7 W
Max Power & Breaker15.6 kW350A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 325A at 25m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A231.83 V (482.99%)0.0 V382.42 V (796.7%)75345.8 WDrop High
2.5 mm²24 A18 A139.1 V (289.79%)0.0 V229.45 V (478.02%)45207.5 WDrop High
4 mm²32 A25 A86.94 V (181.12%)0.0 V143.41 V (298.76%)28254.7 WDrop High
6 mm²41 A32 A57.96 V (120.75%)0.0 V95.6 V (199.18%)18836.5 WDrop High
10 mm²57 A44 A34.77 V (72.45%)13.2 V57.36 V (119.51%)11301.9 WDrop High
16 mm²76 A59 A21.73 V (45.28%)26.3 V35.85 V (74.69%)7063.7 WDrop High
25 mm²101 A78 A13.91 V (28.98%)34.1 V22.95 V (47.8%)4520.7 WDrop High
35 mm²125 A97 A9.94 V (20.7%)38.1 V16.39 V (34.14%)3229.1 WDrop High
50 mm²151 A118 A6.95 V (14.49%)41.0 V11.47 V (23.9%)2260.4 WDrop High
70 mm²192 A150 A4.97 V (10.35%)43.0 V8.19 V (17.07%)1614.6 WDrop High
95 mm²232 A181 A3.66 V (7.63%)44.3 V6.04 V (12.58%)1189.7 WDrop High
120 mm²269 A210 A2.9 V (6.04%)45.1 V4.78 V (9.96%)941.8 WDrop High
150 mm²309 A241 A2.32 V (4.83%)45.7 V3.82 V (7.97%)753.5 WDrop High
185 mm²353 A275 A1.88 V (3.92%)46.1 V3.1 V (6.46%)610.9 W~ ≤5%
240 mm²415 A324 A1.45 V (3.02%)46.6 V2.39 V (4.98%)470.9 W~ ≤5%
300 mm²477 A372 A1.16 V (2.41%)46.8 V1.91 V (3.98%)376.7 W✓ OK (≤3%)
400 mm²570 A445 A0.87 V (1.81%)47.1 V1.43 V (2.99%)282.5 W✓ OK (≤3%)

FAQ — 325 Amp Cable Size at 25 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 325A at 25 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 300 mm² copper cable for 325A over 25m at 48V (voltage drop: 1.16V or 2.41%).

What is the power capacity of 325A at 48V?

At unity power factor, 325A at 48V supports 15.6 kW with a standard 350A circuit breaker.