35 Amp Cable Size at 120 Meters (230V Single-Phase (IEC Europe / UK / AU))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 35 A over 120 m (393.7 ft).

Copper Cable (≤3% Drop)35 mm²Drop: 5.14V (2.23%)
Aluminum Cable (≤3% Drop)50 mm²Drop: 5.93V (2.58%)
Voltage at Load224.9 VLine Loss: 179.8 W
Max Power & Breaker8.05 kW35A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 35A at 120m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A119.84 V (52.1%)110.2 V197.68 V (85.95%)4194.4 WDrop High
2.5 mm²24 A18 A71.9 V (31.26%)158.1 V118.61 V (51.57%)2516.6 WDrop High
4 mm²32 A25 A44.94 V (19.54%)185.1 V74.13 V (32.23%)1572.9 WDrop High
6 mm²41 A32 A29.96 V (13.03%)200.0 V49.42 V (21.49%)1048.6 WDrop High
10 mm²57 A44 A17.98 V (7.82%)212.0 V29.65 V (12.89%)629.2 WDrop High
16 mm²76 A59 A11.23 V (4.88%)218.8 V18.53 V (8.06%)393.2 W~ ≤5%
25 mm²101 A78 A7.19 V (3.13%)222.8 V11.86 V (5.16%)251.7 W~ ≤5%
35 mm²125 A97 A5.14 V (2.23%)224.9 V8.47 V (3.68%)179.8 W✓ OK (≤3%)
50 mm²151 A118 A3.6 V (1.56%)226.4 V5.93 V (2.58%)125.8 W✓ OK (≤3%)
70 mm²192 A150 A2.57 V (1.12%)227.4 V4.24 V (1.84%)89.9 W✓ OK (≤3%)
95 mm²232 A181 A1.89 V (0.82%)228.1 V3.12 V (1.36%)66.2 W✓ OK (≤3%)
120 mm²269 A210 A1.5 V (0.65%)228.5 V2.47 V (1.07%)52.4 W✓ OK (≤3%)
150 mm²309 A241 A1.2 V (0.52%)228.8 V1.98 V (0.86%)41.9 W✓ OK (≤3%)
185 mm²353 A275 A0.97 V (0.42%)229.0 V1.6 V (0.7%)34.0 W✓ OK (≤3%)
240 mm²415 A324 A0.75 V (0.33%)229.3 V1.24 V (0.54%)26.2 W✓ OK (≤3%)
300 mm²477 A372 A0.6 V (0.26%)229.4 V0.99 V (0.43%)21.0 W✓ OK (≤3%)
400 mm²570 A445 A0.45 V (0.2%)229.6 V0.74 V (0.32%)15.7 W✓ OK (≤3%)

FAQ — 35 Amp Cable Size at 120 Meters (230V Single-Phase (IEC Europe / UK / AU))

What mm² cable size is required for 35A at 120 meters (230V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 35 mm² copper cable for 35A over 120m at 230V (voltage drop: 5.14V or 2.23%).

What is the power capacity of 35A at 230V?

At unity power factor, 35A at 230V supports 8.05 kW with a standard 35A circuit breaker.