35 Amp Cable Size at 120 Meters (24V DC (Off-Grid Solar / Industrial Control))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 35 A over 120 m (393.7 ft).

Copper Cable (≤3% Drop)300 mm²Drop: 0.6V (2.5%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 0.74V (3.09%)
Voltage at Load23.4 VLine Loss: 21.0 W
Max Power & Breaker0.84 kW35A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 35A at 120m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A119.84 V (499.33%)0.0 V197.68 V (823.67%)4194.4 WDrop High
2.5 mm²24 A18 A71.9 V (299.6%)0.0 V118.61 V (494.2%)2516.6 WDrop High
4 mm²32 A25 A44.94 V (187.25%)0.0 V74.13 V (308.87%)1572.9 WDrop High
6 mm²41 A32 A29.96 V (124.83%)0.0 V49.42 V (205.92%)1048.6 WDrop High
10 mm²57 A44 A17.98 V (74.9%)6.0 V29.65 V (123.55%)629.2 WDrop High
16 mm²76 A59 A11.23 V (46.81%)12.8 V18.53 V (77.22%)393.2 WDrop High
25 mm²101 A78 A7.19 V (29.96%)16.8 V11.86 V (49.42%)251.7 WDrop High
35 mm²125 A97 A5.14 V (21.4%)18.9 V8.47 V (35.3%)179.8 WDrop High
50 mm²151 A118 A3.6 V (14.98%)20.4 V5.93 V (24.71%)125.8 WDrop High
70 mm²192 A150 A2.57 V (10.7%)21.4 V4.24 V (17.65%)89.9 WDrop High
95 mm²232 A181 A1.89 V (7.88%)22.1 V3.12 V (13.01%)66.2 WDrop High
120 mm²269 A210 A1.5 V (6.24%)22.5 V2.47 V (10.3%)52.4 WDrop High
150 mm²309 A241 A1.2 V (4.99%)22.8 V1.98 V (8.24%)41.9 W~ ≤5%
185 mm²353 A275 A0.97 V (4.05%)23.0 V1.6 V (6.68%)34.0 W~ ≤5%
240 mm²415 A324 A0.75 V (3.12%)23.3 V1.24 V (5.15%)26.2 W~ ≤5%
300 mm²477 A372 A0.6 V (2.5%)23.4 V0.99 V (4.12%)21.0 W✓ OK (≤3%)
400 mm²570 A445 A0.45 V (1.87%)23.6 V0.74 V (3.09%)15.7 W✓ OK (≤3%)

FAQ — 35 Amp Cable Size at 120 Meters (24V DC (Off-Grid Solar / Industrial Control))

What mm² cable size is required for 35A at 120 meters (24V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 300 mm² copper cable for 35A over 120m at 24V (voltage drop: 0.6V or 2.5%).

What is the power capacity of 35A at 24V?

At unity power factor, 35A at 24V supports 0.84 kW with a standard 35A circuit breaker.