35 Amp Cable Size at 120 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 35 A over 120 m (393.7 ft).

Copper Cable (≤3% Drop)16 mm²Drop: 9.73V (2.34%)
Aluminum Cable (≤3% Drop)25 mm²Drop: 10.27V (2.48%)
Voltage at Load405.3 VLine Loss: 589.8 W
Max Power & Breaker25.16 kW35A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 35A at 120m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A103.78 V (25.01%)311.2 V171.2 V (41.25%)6291.6 WDrop High
2.5 mm²24 A18 A62.27 V (15.0%)352.7 V102.72 V (24.75%)3775.0 WDrop High
4 mm²32 A25 A38.92 V (9.38%)376.1 V64.2 V (15.47%)2359.3 WDrop High
6 mm²41 A32 A25.95 V (6.25%)389.1 V42.8 V (10.31%)1572.9 WDrop High
10 mm²57 A44 A15.57 V (3.75%)399.4 V25.68 V (6.19%)943.7 W~ ≤5%
16 mm²76 A59 A9.73 V (2.34%)405.3 V16.05 V (3.87%)589.8 W✓ OK (≤3%)
25 mm²101 A78 A6.23 V (1.5%)408.8 V10.27 V (2.48%)377.5 W✓ OK (≤3%)
35 mm²125 A97 A4.45 V (1.07%)410.6 V7.34 V (1.77%)269.6 W✓ OK (≤3%)
50 mm²151 A118 A3.11 V (0.75%)411.9 V5.14 V (1.24%)188.7 W✓ OK (≤3%)
70 mm²192 A150 A2.22 V (0.54%)412.8 V3.67 V (0.88%)134.8 W✓ OK (≤3%)
95 mm²232 A181 A1.64 V (0.39%)413.4 V2.7 V (0.65%)99.3 W✓ OK (≤3%)
120 mm²269 A210 A1.3 V (0.31%)413.7 V2.14 V (0.52%)78.6 W✓ OK (≤3%)
150 mm²309 A241 A1.04 V (0.25%)414.0 V1.71 V (0.41%)62.9 W✓ OK (≤3%)
185 mm²353 A275 A0.84 V (0.2%)414.2 V1.39 V (0.33%)51.0 W✓ OK (≤3%)
240 mm²415 A324 A0.65 V (0.16%)414.4 V1.07 V (0.26%)39.3 W✓ OK (≤3%)
300 mm²477 A372 A0.52 V (0.13%)414.5 V0.86 V (0.21%)31.5 W✓ OK (≤3%)
400 mm²570 A445 A0.39 V (0.09%)414.6 V0.64 V (0.15%)23.6 W✓ OK (≤3%)

FAQ — 35 Amp Cable Size at 120 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 35A at 120 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 16 mm² copper cable for 35A over 120m at 415V (voltage drop: 9.73V or 2.34%).

What is the power capacity of 35A at 415V?

At unity power factor, 35A at 415V supports 25.16 kW with a standard 35A circuit breaker.