⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

350 Amp Cable Size at 150 Meters (400V Three-Phase (IEC European Grid))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 350 A over 150 m (492.1 ft).

Copper Cable (≤3% Drop)185 mm²Drop: 10.52V (2.63%)
Aluminum Cable (≤3% Drop)300 mm²Drop: 10.7V (2.67%)
Voltage at Load389.5 VLine Loss: 6376.6 W
Max Power & Breaker242.49 kW350A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 350A at 150m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1297.31 V (324.33%)0.0 V2139.95 V (534.99%)786450.0 WDrop High
2.5 mm²24 A18 A778.38 V (194.6%)0.0 V1283.97 V (320.99%)471870.0 WDrop High
4 mm²32 A25 A486.49 V (121.62%)0.0 V802.48 V (200.62%)294918.8 WDrop High
6 mm²41 A32 A324.33 V (81.08%)75.7 V534.99 V (133.75%)196612.5 WDrop High
10 mm²57 A44 A194.6 V (48.65%)205.4 V320.99 V (80.25%)117967.5 WDrop High
16 mm²76 A59 A121.62 V (30.41%)278.4 V200.62 V (50.16%)73729.7 WDrop High
25 mm²101 A78 A77.84 V (19.46%)322.2 V128.4 V (32.1%)47187.0 WDrop High
35 mm²125 A97 A55.6 V (13.9%)344.4 V91.71 V (22.93%)33705.0 WDrop High
50 mm²151 A118 A38.92 V (9.73%)361.1 V64.2 V (16.05%)23593.5 WDrop High
70 mm²192 A150 A27.8 V (6.95%)372.2 V45.86 V (11.46%)16852.5 WDrop High
95 mm²232 A181 A20.48 V (5.12%)379.5 V33.79 V (8.45%)12417.6 WDrop High
120 mm²269 A210 A16.22 V (4.05%)383.8 V26.75 V (6.69%)9830.6 WDrop High
150 mm²309 A241 A12.97 V (3.24%)387.0 V21.4 V (5.35%)7864.5 WDrop High
185 mm²353 A275 A10.52 V (2.63%)389.5 V17.35 V (4.34%)6376.6 W✓ OK (≤3%)
240 mm²415 A324 A8.11 V (2.03%)391.9 V13.37 V (3.34%)4915.3 W✓ OK (≤3%)
300 mm²477 A372 A6.49 V (1.62%)393.5 V10.7 V (2.67%)3932.2 W✓ OK (≤3%)
400 mm²570 A445 A4.86 V (1.22%)395.1 V8.02 V (2.01%)2949.2 W✓ OK (≤3%)

FAQ — 350 Amp Cable Size at 150 Meters (400V Three-Phase (IEC European Grid))

What mm² cable size is required for 350A at 150 meters (400V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 185 mm² copper cable for 350A over 150m at 400V (voltage drop: 10.52V or 2.63%).

What is the power capacity of 350A at 400V?

At unity power factor, 350A at 400V supports 242.49 kW with a standard 350A circuit breaker.