⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

375 Amp Cable Size at 100 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 375 A over 100 m (328.1 ft).

Copper Cable (≤3% Drop)240 mm²Drop: 5.79V (1.4%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 5.73V (1.38%)
Voltage at Load409.2 VLine Loss: 3761.7 W
Max Power & Breaker269.55 kW400A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 375A at 100m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A926.65 V (223.29%)0.0 V1528.53 V (368.32%)601875.0 WDrop High
2.5 mm²24 A18 A555.99 V (133.97%)0.0 V917.12 V (220.99%)361125.0 WDrop High
4 mm²32 A25 A347.49 V (83.73%)67.5 V573.2 V (138.12%)225703.1 WDrop High
6 mm²41 A32 A231.66 V (55.82%)183.3 V382.13 V (92.08%)150468.7 WDrop High
10 mm²57 A44 A139.0 V (33.49%)276.0 V229.28 V (55.25%)90281.2 WDrop High
16 mm²76 A59 A86.87 V (20.93%)328.1 V143.3 V (34.53%)56425.8 WDrop High
25 mm²101 A78 A55.6 V (13.4%)359.4 V91.71 V (22.1%)36112.5 WDrop High
35 mm²125 A97 A39.71 V (9.57%)375.3 V65.51 V (15.79%)25794.6 WDrop High
50 mm²151 A118 A27.8 V (6.7%)387.2 V45.86 V (11.05%)18056.2 WDrop High
70 mm²192 A150 A19.86 V (4.78%)395.1 V32.75 V (7.89%)12897.3 WDrop High
95 mm²232 A181 A14.63 V (3.53%)400.4 V24.13 V (5.82%)9503.3 WDrop High
120 mm²269 A210 A11.58 V (2.79%)403.4 V19.11 V (4.6%)7523.4 WDrop High
150 mm²309 A241 A9.27 V (2.23%)405.7 V15.29 V (3.68%)6018.7 WDrop High
185 mm²353 A275 A7.51 V (1.81%)407.5 V12.39 V (2.99%)4880.1 WDrop High
240 mm²415 A324 A5.79 V (1.4%)409.2 V9.55 V (2.3%)3761.7 W✓ OK (≤3%)
300 mm²477 A372 A4.63 V (1.12%)410.4 V7.64 V (1.84%)3009.4 W✓ OK (≤3%)
400 mm²570 A445 A3.47 V (0.84%)411.5 V5.73 V (1.38%)2257.0 W✓ OK (≤3%)

FAQ — 375 Amp Cable Size at 100 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 375A at 100 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 240 mm² copper cable for 375A over 100m at 415V (voltage drop: 5.79V or 1.4%).

What is the power capacity of 375A at 415V?

At unity power factor, 375A at 415V supports 269.55 kW with a standard 400A circuit breaker.