375 Amp Cable Size at 175 Meters (415V Three-Phase (UK / Australia Industrial))
IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 375 A over 175 m (574.1 ft).
Copper Cable (≤3% Drop)240 mm²Drop: 10.14V (2.44%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 10.03V (2.42%)
Voltage at Load404.9 VLine Loss: 6583.0 W
Max Power & Breaker269.55 kW400A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 375A at 175m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 1621.63 V (390.75%) | 0.0 V | 2674.94 V (644.56%) | 1053281.2 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 972.98 V (234.45%) | 0.0 V | 1604.96 V (386.74%) | 631968.7 W | Drop High |
| 4 mm² | 32 A | 25 A | 608.11 V (146.53%) | 0.0 V | 1003.1 V (241.71%) | 394980.5 W | Drop High |
| 6 mm² | 41 A | 32 A | 405.41 V (97.69%) | 9.6 V | 668.73 V (161.14%) | 263320.3 W | Drop High |
| 10 mm² | 57 A | 44 A | 243.24 V (58.61%) | 171.8 V | 401.24 V (96.68%) | 157992.2 W | Drop High |
| 16 mm² | 76 A | 59 A | 152.03 V (36.63%) | 263.0 V | 250.78 V (60.43%) | 98745.1 W | Drop High |
| 25 mm² | 101 A | 78 A | 97.3 V (23.45%) | 317.7 V | 160.5 V (38.67%) | 63196.9 W | Drop High |
| 35 mm² | 125 A | 97 A | 69.5 V (16.75%) | 345.5 V | 114.64 V (27.62%) | 45140.6 W | Drop High |
| 50 mm² | 151 A | 118 A | 48.65 V (11.72%) | 366.4 V | 80.25 V (19.34%) | 31598.4 W | Drop High |
| 70 mm² | 192 A | 150 A | 34.75 V (8.37%) | 380.3 V | 57.32 V (13.81%) | 22570.3 W | Drop High |
| 95 mm² | 232 A | 181 A | 25.6 V (6.17%) | 389.4 V | 42.24 V (10.18%) | 16630.8 W | Drop High |
| 120 mm² | 269 A | 210 A | 20.27 V (4.88%) | 394.7 V | 33.44 V (8.06%) | 13166.0 W | Drop High |
| 150 mm² | 309 A | 241 A | 16.22 V (3.91%) | 398.8 V | 26.75 V (6.45%) | 10532.8 W | Drop High |
| 185 mm² | 353 A | 275 A | 13.15 V (3.17%) | 401.9 V | 21.69 V (5.23%) | 8540.1 W | Drop High |
| 240 mm² | 415 A | 324 A | 10.14 V (2.44%) | 404.9 V | 16.72 V (4.03%) | 6583.0 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 8.11 V (1.95%) | 406.9 V | 13.37 V (3.22%) | 5266.4 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 6.08 V (1.47%) | 408.9 V | 10.03 V (2.42%) | 3949.8 W | ✓ OK (≤3%) |
FAQ — 375 Amp Cable Size at 175 Meters (415V Three-Phase (UK / Australia Industrial))
What mm² cable size is required for 375A at 175 meters (415V)?
According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 240 mm² copper cable for 375A over 175m at 415V (voltage drop: 10.14V or 2.44%).
What is the power capacity of 375A at 415V?
At unity power factor, 375A at 415V supports 269.55 kW with a standard 400A circuit breaker.
Related Lengths & Currents (415V)
375A · 5m (415V)375A · 10m (415V)375A · 15m (415V)375A · 20m (415V)375A · 25m (415V)375A · 30m (415V)375A · 35m (415V)375A · 40m (415V)375A · 45m (415V)375A · 50m (415V)375A · 60m (415V)375A · 70m (415V)10A · 175m (415V)16A · 175m (415V)20A · 175m (415V)25A · 175m (415V)32A · 175m (415V)40A · 175m (415V)50A · 175m (415V)63A · 175m (415V)80A · 175m (415V)100A · 175m (415V)125A · 175m (415V)160A · 175m (415V)200A · 175m (415V)