375 Amp Cable Size at 175 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 375 A over 175 m (574.1 ft).

Copper Cable (≤3% Drop)240 mm²Drop: 10.14V (1.47%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 10.03V (1.45%)
Voltage at Load679.9 VLine Loss: 6583.0 W
Max Power & Breaker448.17 kW400A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 375A at 175m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1621.63 V (235.02%)0.0 V2674.94 V (387.67%)1053281.2 WDrop High
2.5 mm²24 A18 A972.98 V (141.01%)0.0 V1604.96 V (232.6%)631968.7 WDrop High
4 mm²32 A25 A608.11 V (88.13%)81.9 V1003.1 V (145.38%)394980.5 WDrop High
6 mm²41 A32 A405.41 V (58.75%)284.6 V668.73 V (96.92%)263320.3 WDrop High
10 mm²57 A44 A243.24 V (35.25%)446.8 V401.24 V (58.15%)157992.2 WDrop High
16 mm²76 A59 A152.03 V (22.03%)538.0 V250.78 V (36.34%)98745.1 WDrop High
25 mm²101 A78 A97.3 V (14.1%)592.7 V160.5 V (23.26%)63196.9 WDrop High
35 mm²125 A97 A69.5 V (10.07%)620.5 V114.64 V (16.61%)45140.6 WDrop High
50 mm²151 A118 A48.65 V (7.05%)641.4 V80.25 V (11.63%)31598.4 WDrop High
70 mm²192 A150 A34.75 V (5.04%)655.3 V57.32 V (8.31%)22570.3 WDrop High
95 mm²232 A181 A25.6 V (3.71%)664.4 V42.24 V (6.12%)16630.8 WDrop High
120 mm²269 A210 A20.27 V (2.94%)669.7 V33.44 V (4.85%)13166.0 WDrop High
150 mm²309 A241 A16.22 V (2.35%)673.8 V26.75 V (3.88%)10532.8 WDrop High
185 mm²353 A275 A13.15 V (1.91%)676.9 V21.69 V (3.14%)8540.1 WDrop High
240 mm²415 A324 A10.14 V (1.47%)679.9 V16.72 V (2.42%)6583.0 W✓ OK (≤3%)
300 mm²477 A372 A8.11 V (1.18%)681.9 V13.37 V (1.94%)5266.4 W✓ OK (≤3%)
400 mm²570 A445 A6.08 V (0.88%)683.9 V10.03 V (1.45%)3949.8 W✓ OK (≤3%)

FAQ — 375 Amp Cable Size at 175 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 375A at 175 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 240 mm² copper cable for 375A over 175m at 690V (voltage drop: 10.14V or 1.47%).

What is the power capacity of 375A at 690V?

At unity power factor, 375A at 690V supports 448.17 kW with a standard 400A circuit breaker.