⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

375 Amp Cable Size at 350 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 375 A over 350 m (1148.3 ft).

Copper Cable (≤3% Drop)240 mm²Drop: 20.27V (2.94%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 20.06V (2.91%)
Voltage at Load669.7 VLine Loss: 13166.0 W
Max Power & Breaker448.17 kW400A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 375A at 350m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A3243.27 V (470.04%)0.0 V5349.87 V (775.34%)2106562.5 WDrop High
2.5 mm²24 A18 A1945.96 V (282.02%)0.0 V3209.92 V (465.21%)1263937.5 WDrop High
4 mm²32 A25 A1216.22 V (176.26%)0.0 V2006.2 V (290.75%)789960.9 WDrop High
6 mm²41 A32 A810.82 V (117.51%)0.0 V1337.47 V (193.84%)526640.6 WDrop High
10 mm²57 A44 A486.49 V (70.51%)203.5 V802.48 V (116.3%)315984.4 WDrop High
16 mm²76 A59 A304.06 V (44.07%)385.9 V501.55 V (72.69%)197490.2 WDrop High
25 mm²101 A78 A194.6 V (28.2%)495.4 V320.99 V (46.52%)126393.7 WDrop High
35 mm²125 A97 A139.0 V (20.14%)551.0 V229.28 V (33.23%)90281.2 WDrop High
50 mm²151 A118 A97.3 V (14.1%)592.7 V160.5 V (23.26%)63196.9 WDrop High
70 mm²192 A150 A69.5 V (10.07%)620.5 V114.64 V (16.61%)45140.6 WDrop High
95 mm²232 A181 A51.21 V (7.42%)638.8 V84.47 V (12.24%)33261.5 WDrop High
120 mm²269 A210 A40.54 V (5.88%)649.5 V66.87 V (9.69%)26332.0 WDrop High
150 mm²309 A241 A32.43 V (4.7%)657.6 V53.5 V (7.75%)21065.6 WDrop High
185 mm²353 A275 A26.3 V (3.81%)663.7 V43.38 V (6.29%)17080.2 WDrop High
240 mm²415 A324 A20.27 V (2.94%)669.7 V33.44 V (4.85%)13166.0 W✓ OK (≤3%)
300 mm²477 A372 A16.22 V (2.35%)673.8 V26.75 V (3.88%)10532.8 W✓ OK (≤3%)
400 mm²570 A445 A12.16 V (1.76%)677.8 V20.06 V (2.91%)7899.6 W✓ OK (≤3%)

FAQ — 375 Amp Cable Size at 350 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 375A at 350 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 240 mm² copper cable for 375A over 350m at 690V (voltage drop: 20.27V or 2.94%).

What is the power capacity of 375A at 690V?

At unity power factor, 375A at 690V supports 448.17 kW with a standard 400A circuit breaker.