⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

375 Amp Cable Size at 80 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 375 A over 80 m (262.5 ft).

Copper Cable (≤3% Drop)240 mm²Drop: 4.63V (1.12%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 4.59V (1.1%)
Voltage at Load410.4 VLine Loss: 3009.4 W
Max Power & Breaker269.55 kW400A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 375A at 80m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A741.32 V (178.63%)0.0 V1222.83 V (294.66%)481500.0 WDrop High
2.5 mm²24 A18 A444.79 V (107.18%)0.0 V733.7 V (176.79%)288900.0 WDrop High
4 mm²32 A25 A277.99 V (66.99%)137.0 V458.56 V (110.5%)180562.5 WDrop High
6 mm²41 A32 A185.33 V (44.66%)229.7 V305.71 V (73.66%)120375.0 WDrop High
10 mm²57 A44 A111.2 V (26.79%)303.8 V183.42 V (44.2%)72225.0 WDrop High
16 mm²76 A59 A69.5 V (16.75%)345.5 V114.64 V (27.62%)45140.6 WDrop High
25 mm²101 A78 A44.48 V (10.72%)370.5 V73.37 V (17.68%)28890.0 WDrop High
35 mm²125 A97 A31.77 V (7.66%)383.2 V52.41 V (12.63%)20635.7 WDrop High
50 mm²151 A118 A22.24 V (5.36%)392.8 V36.68 V (8.84%)14445.0 WDrop High
70 mm²192 A150 A15.89 V (3.83%)399.1 V26.2 V (6.31%)10317.9 WDrop High
95 mm²232 A181 A11.71 V (2.82%)403.3 V19.31 V (4.65%)7602.6 WDrop High
120 mm²269 A210 A9.27 V (2.23%)405.7 V15.29 V (3.68%)6018.8 WDrop High
150 mm²309 A241 A7.41 V (1.79%)407.6 V12.23 V (2.95%)4815.0 WDrop High
185 mm²353 A275 A6.01 V (1.45%)409.0 V9.91 V (2.39%)3904.1 WDrop High
240 mm²415 A324 A4.63 V (1.12%)410.4 V7.64 V (1.84%)3009.4 W✓ OK (≤3%)
300 mm²477 A372 A3.71 V (0.89%)411.3 V6.11 V (1.47%)2407.5 W✓ OK (≤3%)
400 mm²570 A445 A2.78 V (0.67%)412.2 V4.59 V (1.1%)1805.6 W✓ OK (≤3%)

FAQ — 375 Amp Cable Size at 80 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 375A at 80 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 240 mm² copper cable for 375A over 80m at 415V (voltage drop: 4.63V or 1.12%).

What is the power capacity of 375A at 415V?

At unity power factor, 375A at 415V supports 269.55 kW with a standard 400A circuit breaker.