400 Amp Cable Size at 100 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 400 A over 100 m (328.1 ft).

Copper Cable (≤3% Drop)240 mm²Drop: 6.18V (0.9%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 6.11V (0.89%)
Voltage at Load683.8 VLine Loss: 4280.0 W
Max Power & Breaker478.05 kW400A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 400A at 100m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A988.42 V (143.25%)0.0 V1630.44 V (236.3%)684800.0 WDrop High
2.5 mm²24 A18 A593.05 V (85.95%)96.9 V978.26 V (141.78%)410880.0 WDrop High
4 mm²32 A25 A370.66 V (53.72%)319.3 V611.41 V (88.61%)256800.0 WDrop High
6 mm²41 A32 A247.11 V (35.81%)442.9 V407.61 V (59.07%)171200.0 WDrop High
10 mm²57 A44 A148.26 V (21.49%)541.7 V244.57 V (35.44%)102720.0 WDrop High
16 mm²76 A59 A92.66 V (13.43%)597.3 V152.85 V (22.15%)64200.0 WDrop High
25 mm²101 A78 A59.31 V (8.59%)630.7 V97.83 V (14.18%)41088.0 WDrop High
35 mm²125 A97 A42.36 V (6.14%)647.6 V69.88 V (10.13%)29348.6 WDrop High
50 mm²151 A118 A29.65 V (4.3%)660.3 V48.91 V (7.09%)20544.0 WDrop High
70 mm²192 A150 A21.18 V (3.07%)668.8 V34.94 V (5.06%)14674.3 WDrop High
95 mm²232 A181 A15.61 V (2.26%)674.4 V25.74 V (3.73%)10812.6 WDrop High
120 mm²269 A210 A12.36 V (1.79%)677.6 V20.38 V (2.95%)8560.0 WDrop High
150 mm²309 A241 A9.88 V (1.43%)680.1 V16.3 V (2.36%)6848.0 WDrop High
185 mm²353 A275 A8.01 V (1.16%)682.0 V13.22 V (1.92%)5552.4 WDrop High
240 mm²415 A324 A6.18 V (0.9%)683.8 V10.19 V (1.48%)4280.0 W✓ OK (≤3%)
300 mm²477 A372 A4.94 V (0.72%)685.1 V8.15 V (1.18%)3424.0 W✓ OK (≤3%)
400 mm²570 A445 A3.71 V (0.54%)686.3 V6.11 V (0.89%)2568.0 W✓ OK (≤3%)

FAQ — 400 Amp Cable Size at 100 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 400A at 100 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 240 mm² copper cable for 400A over 100m at 690V (voltage drop: 6.18V or 0.9%).

What is the power capacity of 400A at 690V?

At unity power factor, 400A at 690V supports 478.05 kW with a standard 400A circuit breaker.