400 Amp Cable Size at 250 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 400 A over 250 m (820.2 ft).

Copper Cable (≤3% Drop)240 mm²Drop: 15.44V (2.24%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 15.29V (2.22%)
Voltage at Load674.6 VLine Loss: 10700.0 W
Max Power & Breaker478.05 kW400A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 400A at 250m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A2471.06 V (358.12%)0.0 V4076.09 V (590.74%)1712000.0 WDrop High
2.5 mm²24 A18 A1482.64 V (214.87%)0.0 V2445.66 V (354.44%)1027200.0 WDrop High
4 mm²32 A25 A926.65 V (134.3%)0.0 V1528.53 V (221.53%)642000.0 WDrop High
6 mm²41 A32 A617.76 V (89.53%)72.2 V1019.02 V (147.68%)428000.0 WDrop High
10 mm²57 A44 A370.66 V (53.72%)319.3 V611.41 V (88.61%)256800.0 WDrop High
16 mm²76 A59 A231.66 V (33.57%)458.3 V382.13 V (55.38%)160500.0 WDrop High
25 mm²101 A78 A148.26 V (21.49%)541.7 V244.57 V (35.44%)102720.0 WDrop High
35 mm²125 A97 A105.9 V (15.35%)584.1 V174.69 V (25.32%)73371.4 WDrop High
50 mm²151 A118 A74.13 V (10.74%)615.9 V122.28 V (17.72%)51360.0 WDrop High
70 mm²192 A150 A52.95 V (7.67%)637.0 V87.34 V (12.66%)36685.7 WDrop High
95 mm²232 A181 A39.02 V (5.65%)651.0 V64.36 V (9.33%)27031.6 WDrop High
120 mm²269 A210 A30.89 V (4.48%)659.1 V50.95 V (7.38%)21400.0 WDrop High
150 mm²309 A241 A24.71 V (3.58%)665.3 V40.76 V (5.91%)17120.0 WDrop High
185 mm²353 A275 A20.04 V (2.9%)670.0 V33.05 V (4.79%)13881.1 WDrop High
240 mm²415 A324 A15.44 V (2.24%)674.6 V25.48 V (3.69%)10700.0 W✓ OK (≤3%)
300 mm²477 A372 A12.36 V (1.79%)677.6 V20.38 V (2.95%)8560.0 W✓ OK (≤3%)
400 mm²570 A445 A9.27 V (1.34%)680.7 V15.29 V (2.22%)6420.0 W✓ OK (≤3%)

FAQ — 400 Amp Cable Size at 250 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 400A at 250 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 240 mm² copper cable for 400A over 250m at 690V (voltage drop: 15.44V or 2.24%).

What is the power capacity of 400A at 690V?

At unity power factor, 400A at 690V supports 478.05 kW with a standard 400A circuit breaker.