425 Amp Cable Size at 100 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 425 A over 100 m (328.1 ft).

Copper Cable (≤3% Drop)300 mm²Drop: 5.25V (0.76%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 6.5V (0.94%)
Voltage at Load684.7 VLine Loss: 3865.4 W
Max Power & Breaker507.92 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 425A at 100m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1050.2 V (152.2%)0.0 V1732.34 V (251.06%)773075.0 WDrop High
2.5 mm²24 A18 A630.12 V (91.32%)59.9 V1039.4 V (150.64%)463845.0 WDrop High
4 mm²32 A25 A393.83 V (57.08%)296.2 V649.63 V (94.15%)289903.1 WDrop High
6 mm²41 A32 A262.55 V (38.05%)427.4 V433.08 V (62.77%)193268.7 WDrop High
10 mm²57 A44 A157.53 V (22.83%)532.5 V259.85 V (37.66%)115961.2 WDrop High
16 mm²76 A59 A98.46 V (14.27%)591.5 V162.41 V (23.54%)72475.8 WDrop High
25 mm²101 A78 A63.01 V (9.13%)627.0 V103.94 V (15.06%)46384.5 WDrop High
35 mm²125 A97 A45.01 V (6.52%)645.0 V74.24 V (10.76%)33131.8 WDrop High
50 mm²151 A118 A31.51 V (4.57%)658.5 V51.97 V (7.53%)23192.2 WDrop High
70 mm²192 A150 A22.5 V (3.26%)667.5 V37.12 V (5.38%)16565.9 WDrop High
95 mm²232 A181 A16.58 V (2.4%)673.4 V27.35 V (3.96%)12206.4 WDrop High
120 mm²269 A210 A13.13 V (1.9%)676.9 V21.65 V (3.14%)9663.4 WDrop High
150 mm²309 A241 A10.5 V (1.52%)679.5 V17.32 V (2.51%)7730.7 WDrop High
185 mm²353 A275 A8.52 V (1.23%)681.5 V14.05 V (2.04%)6268.2 WDrop High
240 mm²415 A324 A6.56 V (0.95%)683.4 V10.83 V (1.57%)4831.7 WDrop High
300 mm²477 A372 A5.25 V (0.76%)684.7 V8.66 V (1.26%)3865.4 W✓ OK (≤3%)
400 mm²570 A445 A3.94 V (0.57%)686.1 V6.5 V (0.94%)2899.0 W✓ OK (≤3%)

FAQ — 425 Amp Cable Size at 100 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 425A at 100 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 300 mm² copper cable for 425A over 100m at 690V (voltage drop: 5.25V or 0.76%).

What is the power capacity of 425A at 690V?

At unity power factor, 425A at 690V supports 507.92 kW with a standard 450A circuit breaker.