425 Amp Cable Size at 175 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 425 A over 175 m (574.1 ft).

Copper Cable (≤3% Drop)300 mm²Drop: 9.19V (1.33%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 11.37V (1.65%)
Voltage at Load680.8 VLine Loss: 6764.4 W
Max Power & Breaker507.92 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 425A at 175m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1837.85 V (266.36%)0.0 V3031.59 V (439.36%)1352881.2 WDrop High
2.5 mm²24 A18 A1102.71 V (159.81%)0.0 V1818.96 V (263.62%)811728.7 WDrop High
4 mm²32 A25 A689.19 V (99.88%)0.8 V1136.85 V (164.76%)507330.5 WDrop High
6 mm²41 A32 A459.46 V (66.59%)230.5 V757.9 V (109.84%)338220.3 WDrop High
10 mm²57 A44 A275.68 V (39.95%)414.3 V454.74 V (65.9%)202932.2 WDrop High
16 mm²76 A59 A172.3 V (24.97%)517.7 V284.21 V (41.19%)126832.6 WDrop High
25 mm²101 A78 A110.27 V (15.98%)579.7 V181.9 V (26.36%)81172.9 WDrop High
35 mm²125 A97 A78.77 V (11.42%)611.2 V129.93 V (18.83%)57980.6 WDrop High
50 mm²151 A118 A55.14 V (7.99%)634.9 V90.95 V (13.18%)40586.4 WDrop High
70 mm²192 A150 A39.38 V (5.71%)650.6 V64.96 V (9.41%)28990.3 WDrop High
95 mm²232 A181 A29.02 V (4.21%)661.0 V47.87 V (6.94%)21361.3 WDrop High
120 mm²269 A210 A22.97 V (3.33%)667.0 V37.89 V (5.49%)16911.0 WDrop High
150 mm²309 A241 A18.38 V (2.66%)671.6 V30.32 V (4.39%)13528.8 WDrop High
185 mm²353 A275 A14.9 V (2.16%)675.1 V24.58 V (3.56%)10969.3 WDrop High
240 mm²415 A324 A11.49 V (1.66%)678.5 V18.95 V (2.75%)8455.5 WDrop High
300 mm²477 A372 A9.19 V (1.33%)680.8 V15.16 V (2.2%)6764.4 W✓ OK (≤3%)
400 mm²570 A445 A6.89 V (1.0%)683.1 V11.37 V (1.65%)5073.3 W✓ OK (≤3%)

FAQ — 425 Amp Cable Size at 175 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 425A at 175 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 300 mm² copper cable for 425A over 175m at 690V (voltage drop: 9.19V or 1.33%).

What is the power capacity of 425A at 690V?

At unity power factor, 425A at 690V supports 507.92 kW with a standard 450A circuit breaker.