⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

425 Amp Cable Size at 20 Meters (24V DC (Off-Grid Solar / Industrial Control))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 425 A over 20 m (65.6 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 0.46V (1.9%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 1.5V (6.25%)
Voltage at Load23.5 VLine Loss: 193.2 W
Max Power & Breaker10.2 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 425A at 20m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A242.53 V (1010.56%)0.0 V400.07 V (1666.94%)103076.7 WDrop High
2.5 mm²24 A18 A145.52 V (606.33%)0.0 V240.04 V (1000.17%)61846.0 WDrop High
4 mm²32 A25 A90.95 V (378.96%)0.0 V150.03 V (625.1%)38653.8 WDrop High
6 mm²41 A32 A60.63 V (252.64%)0.0 V100.02 V (416.74%)25769.2 WDrop High
10 mm²57 A44 A36.38 V (151.58%)0.0 V60.01 V (250.04%)15461.5 WDrop High
16 mm²76 A59 A22.74 V (94.74%)1.3 V37.51 V (156.28%)9663.4 WDrop High
25 mm²101 A78 A14.55 V (60.63%)9.4 V24.0 V (100.02%)6184.6 WDrop High
35 mm²125 A97 A10.39 V (43.31%)13.6 V17.15 V (71.44%)4417.6 WDrop High
50 mm²151 A118 A7.28 V (30.32%)16.7 V12.0 V (50.01%)3092.3 WDrop High
70 mm²192 A150 A5.2 V (21.65%)18.8 V8.57 V (35.72%)2208.8 WDrop High
95 mm²232 A181 A3.83 V (15.96%)20.2 V6.32 V (26.32%)1627.5 WDrop High
120 mm²269 A210 A3.03 V (12.63%)21.0 V5.0 V (20.84%)1288.5 WDrop High
150 mm²309 A241 A2.43 V (10.11%)21.6 V4.0 V (16.67%)1030.8 WDrop High
185 mm²353 A275 A1.97 V (8.19%)22.0 V3.24 V (13.52%)835.8 WDrop High
240 mm²415 A324 A1.52 V (6.32%)22.5 V2.5 V (10.42%)644.2 WDrop High
300 mm²477 A372 A1.21 V (5.05%)22.8 V2.0 V (8.33%)515.4 WDrop High
400 mm²570 A445 A0.91 V (3.79%)23.1 V1.5 V (6.25%)386.5 W~ ≤5%

FAQ — 425 Amp Cable Size at 20 Meters (24V DC (Off-Grid Solar / Industrial Control))

What mm² cable size is required for 425A at 20 meters (24V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 425A over 20m at 24V (voltage drop: 0.46V or 1.9%).

What is the power capacity of 425A at 24V?

At unity power factor, 425A at 24V supports 10.2 kW with a standard 450A circuit breaker.