425 Amp Cable Size at 15 Meters (24V DC (Off-Grid Solar / Industrial Control))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 425 A over 15 m (49.2 ft).

Copper Cable (≤3% Drop)400 mm²Drop: 0.68V (2.84%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 1.13V (4.69%)
Voltage at Load23.3 VLine Loss: 289.9 W
Max Power & Breaker10.2 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 425A at 15m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A181.9 V (757.92%)0.0 V300.05 V (1250.21%)77307.5 WDrop High
2.5 mm²24 A18 A109.14 V (454.75%)0.0 V180.03 V (750.12%)46384.5 WDrop High
4 mm²32 A25 A68.21 V (284.22%)0.0 V112.52 V (468.83%)28990.3 WDrop High
6 mm²41 A32 A45.48 V (189.48%)0.0 V75.01 V (312.55%)19326.9 WDrop High
10 mm²57 A44 A27.29 V (113.69%)0.0 V45.01 V (187.53%)11596.1 WDrop High
16 mm²76 A59 A17.05 V (71.05%)6.9 V28.13 V (117.21%)7247.6 WDrop High
25 mm²101 A78 A10.91 V (45.48%)13.1 V18.0 V (75.01%)4638.4 WDrop High
35 mm²125 A97 A7.8 V (32.48%)16.2 V12.86 V (53.58%)3313.2 WDrop High
50 mm²151 A118 A5.46 V (22.74%)18.5 V9.0 V (37.51%)2319.2 WDrop High
70 mm²192 A150 A3.9 V (16.24%)20.1 V6.43 V (26.79%)1656.6 WDrop High
95 mm²232 A181 A2.87 V (11.97%)21.1 V4.74 V (19.74%)1220.6 WDrop High
120 mm²269 A210 A2.27 V (9.47%)21.7 V3.75 V (15.63%)966.3 WDrop High
150 mm²309 A241 A1.82 V (7.58%)22.2 V3.0 V (12.5%)773.1 WDrop High
185 mm²353 A275 A1.47 V (6.15%)22.5 V2.43 V (10.14%)626.8 WDrop High
240 mm²415 A324 A1.14 V (4.74%)22.9 V1.88 V (7.81%)483.2 WDrop High
300 mm²477 A372 A0.91 V (3.79%)23.1 V1.5 V (6.25%)386.5 W~ ≤5%
400 mm²570 A445 A0.68 V (2.84%)23.3 V1.13 V (4.69%)289.9 W✓ OK (≤3%)

FAQ — 425 Amp Cable Size at 15 Meters (24V DC (Off-Grid Solar / Industrial Control))

What mm² cable size is required for 425A at 15 meters (24V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 400 mm² copper cable for 425A over 15m at 24V (voltage drop: 0.68V or 2.84%).

What is the power capacity of 425A at 24V?

At unity power factor, 425A at 24V supports 10.2 kW with a standard 450A circuit breaker.