425 Amp Cable Size at 60 Meters (24V DC (Off-Grid Solar / Industrial Control))
IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 425 A over 60 m (196.9 ft).
Copper Cable (≤3% Drop)4× 400 mm²Drop: 0.68V (2.84%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 4.5V (18.75%)
Voltage at Load23.3 VLine Loss: 289.9 W
Max Power & Breaker10.2 kW450A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 425A at 60m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 727.6 V (3031.67%) | 0.0 V | 1200.2 V (5000.83%) | 309230.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 436.56 V (1819.0%) | 0.0 V | 720.12 V (3000.5%) | 185538.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 272.85 V (1136.88%) | 0.0 V | 450.07 V (1875.31%) | 115961.2 W | Drop High |
| 6 mm² | 41 A | 32 A | 181.9 V (757.92%) | 0.0 V | 300.05 V (1250.21%) | 77307.5 W | Drop High |
| 10 mm² | 57 A | 44 A | 109.14 V (454.75%) | 0.0 V | 180.03 V (750.12%) | 46384.5 W | Drop High |
| 16 mm² | 76 A | 59 A | 68.21 V (284.22%) | 0.0 V | 112.52 V (468.83%) | 28990.3 W | Drop High |
| 25 mm² | 101 A | 78 A | 43.66 V (181.9%) | 0.0 V | 72.01 V (300.05%) | 18553.8 W | Drop High |
| 35 mm² | 125 A | 97 A | 31.18 V (129.93%) | 0.0 V | 51.44 V (214.32%) | 13252.7 W | Drop High |
| 50 mm² | 151 A | 118 A | 21.83 V (90.95%) | 2.2 V | 36.01 V (150.02%) | 9276.9 W | Drop High |
| 70 mm² | 192 A | 150 A | 15.59 V (64.96%) | 8.4 V | 25.72 V (107.16%) | 6626.4 W | Drop High |
| 95 mm² | 232 A | 181 A | 11.49 V (47.87%) | 12.5 V | 18.95 V (78.96%) | 4882.6 W | Drop High |
| 120 mm² | 269 A | 210 A | 9.09 V (37.9%) | 14.9 V | 15.0 V (62.51%) | 3865.4 W | Drop High |
| 150 mm² | 309 A | 241 A | 7.28 V (30.32%) | 16.7 V | 12.0 V (50.01%) | 3092.3 W | Drop High |
| 185 mm² | 353 A | 275 A | 5.9 V (24.58%) | 18.1 V | 9.73 V (40.55%) | 2507.3 W | Drop High |
| 240 mm² | 415 A | 324 A | 4.55 V (18.95%) | 19.5 V | 7.5 V (31.26%) | 1932.7 W | Drop High |
| 300 mm² | 477 A | 372 A | 3.64 V (15.16%) | 20.4 V | 6.0 V (25.0%) | 1546.2 W | Drop High |
| 400 mm² | 570 A | 445 A | 2.73 V (11.37%) | 21.3 V | 4.5 V (18.75%) | 1159.6 W | Drop High |
FAQ — 425 Amp Cable Size at 60 Meters (24V DC (Off-Grid Solar / Industrial Control))
What mm² cable size is required for 425A at 60 meters (24V)?
According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 4× 400 mm² copper cable for 425A over 60m at 24V (voltage drop: 0.68V or 2.84%).
What is the power capacity of 425A at 24V?
At unity power factor, 425A at 24V supports 10.2 kW with a standard 450A circuit breaker.
Related Lengths & Currents (24V)
425A · 5m (24V)425A · 10m (24V)425A · 15m (24V)425A · 20m (24V)425A · 25m (24V)425A · 30m (24V)425A · 35m (24V)425A · 40m (24V)425A · 45m (24V)425A · 50m (24V)425A · 70m (24V)10A · 60m (24V)16A · 60m (24V)20A · 60m (24V)25A · 60m (24V)32A · 60m (24V)40A · 60m (24V)50A · 60m (24V)63A · 60m (24V)80A · 60m (24V)100A · 60m (24V)125A · 60m (24V)160A · 60m (24V)200A · 60m (24V)