425 Amp Cable Size at 5 Meters (24V DC (Off-Grid Solar / Industrial Control))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 425 A over 5 m (16.4 ft).

Copper Cable (≤3% Drop)300 mm²Drop: 0.3V (1.26%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 0.38V (1.56%)
Voltage at Load23.7 VLine Loss: 128.8 W
Max Power & Breaker10.2 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 425A at 5m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A60.63 V (252.64%)0.0 V100.02 V (416.74%)25769.2 WDrop High
2.5 mm²24 A18 A36.38 V (151.58%)0.0 V60.01 V (250.04%)15461.5 WDrop High
4 mm²32 A25 A22.74 V (94.74%)1.3 V37.51 V (156.28%)9663.4 WDrop High
6 mm²41 A32 A15.16 V (63.16%)8.8 V25.0 V (104.18%)6442.3 WDrop High
10 mm²57 A44 A9.09 V (37.9%)14.9 V15.0 V (62.51%)3865.4 WDrop High
16 mm²76 A59 A5.68 V (23.68%)18.3 V9.38 V (39.07%)2415.9 WDrop High
25 mm²101 A78 A3.64 V (15.16%)20.4 V6.0 V (25.0%)1546.2 WDrop High
35 mm²125 A97 A2.6 V (10.83%)21.4 V4.29 V (17.86%)1104.4 WDrop High
50 mm²151 A118 A1.82 V (7.58%)22.2 V3.0 V (12.5%)773.1 WDrop High
70 mm²192 A150 A1.3 V (5.41%)22.7 V2.14 V (8.93%)552.2 WDrop High
95 mm²232 A181 A0.96 V (3.99%)23.0 V1.58 V (6.58%)406.9 WDrop High
120 mm²269 A210 A0.76 V (3.16%)23.2 V1.25 V (5.21%)322.1 WDrop High
150 mm²309 A241 A0.61 V (2.53%)23.4 V1.0 V (4.17%)257.7 WDrop High
185 mm²353 A275 A0.49 V (2.05%)23.5 V0.81 V (3.38%)208.9 WDrop High
240 mm²415 A324 A0.38 V (1.58%)23.6 V0.63 V (2.6%)161.1 WDrop High
300 mm²477 A372 A0.3 V (1.26%)23.7 V0.5 V (2.08%)128.8 W✓ OK (≤3%)
400 mm²570 A445 A0.23 V (0.95%)23.8 V0.38 V (1.56%)96.6 W✓ OK (≤3%)

FAQ — 425 Amp Cable Size at 5 Meters (24V DC (Off-Grid Solar / Industrial Control))

What mm² cable size is required for 425A at 5 meters (24V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 300 mm² copper cable for 425A over 5m at 24V (voltage drop: 0.3V or 1.26%).

What is the power capacity of 425A at 24V?

At unity power factor, 425A at 24V supports 10.2 kW with a standard 450A circuit breaker.