425 Amp Cable Size at 250 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 425 A over 250 m (820.2 ft).

Copper Cable (≤3% Drop)300 mm²Drop: 13.13V (1.9%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 16.24V (2.35%)
Voltage at Load676.9 VLine Loss: 9663.4 W
Max Power & Breaker507.92 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 425A at 250m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A2625.5 V (380.51%)0.0 V4330.85 V (627.66%)1932687.5 WDrop High
2.5 mm²24 A18 A1575.3 V (228.3%)0.0 V2598.51 V (376.6%)1159612.5 WDrop High
4 mm²32 A25 A984.56 V (142.69%)0.0 V1624.07 V (235.37%)724757.8 WDrop High
6 mm²41 A32 A656.38 V (95.13%)33.6 V1082.71 V (156.91%)483171.9 WDrop High
10 mm²57 A44 A393.83 V (57.08%)296.2 V649.63 V (94.15%)289903.1 WDrop High
16 mm²76 A59 A246.14 V (35.67%)443.9 V406.02 V (58.84%)181189.5 WDrop High
25 mm²101 A78 A157.53 V (22.83%)532.5 V259.85 V (37.66%)115961.2 WDrop High
35 mm²125 A97 A112.52 V (16.31%)577.5 V185.61 V (26.9%)82829.5 WDrop High
50 mm²151 A118 A78.77 V (11.42%)611.2 V129.93 V (18.83%)57980.6 WDrop High
70 mm²192 A150 A56.26 V (8.15%)633.7 V92.8 V (13.45%)41414.7 WDrop High
95 mm²232 A181 A41.46 V (6.01%)648.5 V68.38 V (9.91%)30516.1 WDrop High
120 mm²269 A210 A32.82 V (4.76%)657.2 V54.14 V (7.85%)24158.6 WDrop High
150 mm²309 A241 A26.26 V (3.81%)663.7 V43.31 V (6.28%)19326.9 WDrop High
185 mm²353 A275 A21.29 V (3.09%)668.7 V35.11 V (5.09%)15670.4 WDrop High
240 mm²415 A324 A16.41 V (2.38%)673.6 V27.07 V (3.92%)12079.3 WDrop High
300 mm²477 A372 A13.13 V (1.9%)676.9 V21.65 V (3.14%)9663.4 W✓ OK (≤3%)
400 mm²570 A445 A9.85 V (1.43%)680.2 V16.24 V (2.35%)7247.6 W✓ OK (≤3%)

FAQ — 425 Amp Cable Size at 250 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 425A at 250 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 300 mm² copper cable for 425A over 250m at 690V (voltage drop: 13.13V or 1.9%).

What is the power capacity of 425A at 690V?

At unity power factor, 425A at 690V supports 507.92 kW with a standard 450A circuit breaker.