425 Amp Cable Size at 300 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 425 A over 300 m (984.3 ft).

Copper Cable (≤3% Drop)300 mm²Drop: 15.75V (2.28%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 19.49V (2.82%)
Voltage at Load674.2 VLine Loss: 11596.1 W
Max Power & Breaker507.92 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 425A at 300m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A3150.6 V (456.61%)0.0 V5197.02 V (753.19%)2319225.0 WDrop High
2.5 mm²24 A18 A1890.36 V (273.97%)0.0 V3118.21 V (451.91%)1391535.0 WDrop High
4 mm²32 A25 A1181.48 V (171.23%)0.0 V1948.88 V (282.45%)869709.4 WDrop High
6 mm²41 A32 A787.65 V (114.15%)0.0 V1299.25 V (188.3%)579806.2 WDrop High
10 mm²57 A44 A472.59 V (68.49%)217.4 V779.55 V (112.98%)347883.8 WDrop High
16 mm²76 A59 A295.37 V (42.81%)394.6 V487.22 V (70.61%)217427.3 WDrop High
25 mm²101 A78 A189.04 V (27.4%)501.0 V311.82 V (45.19%)139153.5 WDrop High
35 mm²125 A97 A135.03 V (19.57%)555.0 V222.73 V (32.28%)99395.4 WDrop High
50 mm²151 A118 A94.52 V (13.7%)595.5 V155.91 V (22.6%)69576.7 WDrop High
70 mm²192 A150 A67.51 V (9.78%)622.5 V111.36 V (16.14%)49697.7 WDrop High
95 mm²232 A181 A49.75 V (7.21%)640.3 V82.06 V (11.89%)36619.3 WDrop High
120 mm²269 A210 A39.38 V (5.71%)650.6 V64.96 V (9.41%)28990.3 WDrop High
150 mm²309 A241 A31.51 V (4.57%)658.5 V51.97 V (7.53%)23192.2 WDrop High
185 mm²353 A275 A25.55 V (3.7%)664.5 V42.14 V (6.11%)18804.5 WDrop High
240 mm²415 A324 A19.69 V (2.85%)670.3 V32.48 V (4.71%)14495.2 WDrop High
300 mm²477 A372 A15.75 V (2.28%)674.2 V25.99 V (3.77%)11596.1 W✓ OK (≤3%)
400 mm²570 A445 A11.81 V (1.71%)678.2 V19.49 V (2.82%)8697.1 W✓ OK (≤3%)

FAQ — 425 Amp Cable Size at 300 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 425A at 300 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 300 mm² copper cable for 425A over 300m at 690V (voltage drop: 15.75V or 2.28%).

What is the power capacity of 425A at 690V?

At unity power factor, 425A at 690V supports 507.92 kW with a standard 450A circuit breaker.