425 Amp Cable Size at 350 Meters (400V Three-Phase (IEC European Grid))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 425 A over 350 m (1148.3 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 6.89V (1.73%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 22.74V (5.68%)
Voltage at Load393.1 VLine Loss: 5073.3 W
Max Power & Breaker294.45 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 425A at 350m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A3675.7 V (918.93%)0.0 V6063.19 V (1515.8%)2705762.5 WDrop High
2.5 mm²24 A18 A2205.42 V (551.36%)0.0 V3637.91 V (909.48%)1623457.5 WDrop High
4 mm²32 A25 A1378.39 V (344.6%)0.0 V2273.7 V (568.42%)1014660.9 WDrop High
6 mm²41 A32 A918.93 V (229.73%)0.0 V1515.8 V (378.95%)676440.6 WDrop High
10 mm²57 A44 A551.36 V (137.84%)0.0 V909.48 V (227.37%)405864.4 WDrop High
16 mm²76 A59 A344.6 V (86.15%)55.4 V568.42 V (142.11%)253665.2 WDrop High
25 mm²101 A78 A220.54 V (55.14%)179.5 V363.79 V (90.95%)162345.8 WDrop High
35 mm²125 A97 A157.53 V (39.38%)242.5 V259.85 V (64.96%)115961.2 WDrop High
50 mm²151 A118 A110.27 V (27.57%)289.7 V181.9 V (45.47%)81172.9 WDrop High
70 mm²192 A150 A78.77 V (19.69%)321.2 V129.93 V (32.48%)57980.6 WDrop High
95 mm²232 A181 A58.04 V (14.51%)342.0 V95.73 V (23.93%)42722.6 WDrop High
120 mm²269 A210 A45.95 V (11.49%)354.1 V75.79 V (18.95%)33822.0 WDrop High
150 mm²309 A241 A36.76 V (9.19%)363.2 V60.63 V (15.16%)27057.6 WDrop High
185 mm²353 A275 A29.8 V (7.45%)370.2 V49.16 V (12.29%)21938.6 WDrop High
240 mm²415 A324 A22.97 V (5.74%)377.0 V37.89 V (9.47%)16911.0 WDrop High
300 mm²477 A372 A18.38 V (4.59%)381.6 V30.32 V (7.58%)13528.8 W~ ≤5%
400 mm²570 A445 A13.78 V (3.45%)386.2 V22.74 V (5.68%)10146.6 W~ ≤5%

FAQ — 425 Amp Cable Size at 350 Meters (400V Three-Phase (IEC European Grid))

What mm² cable size is required for 425A at 350 meters (400V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 425A over 350m at 400V (voltage drop: 6.89V or 1.73%).

What is the power capacity of 425A at 400V?

At unity power factor, 425A at 400V supports 294.45 kW with a standard 450A circuit breaker.