425 Amp Cable Size at 500 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 425 A over 500 m (1640.4 ft).

Copper Cable (≤3% Drop)400 mm²Drop: 19.69V (2.85%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 32.48V (4.71%)
Voltage at Load670.3 VLine Loss: 14495.2 W
Max Power & Breaker507.92 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 425A at 500m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A5251.0 V (761.01%)0.0 V8661.7 V (1255.32%)3865375.0 WDrop High
2.5 mm²24 A18 A3150.6 V (456.61%)0.0 V5197.02 V (753.19%)2319225.0 WDrop High
4 mm²32 A25 A1969.13 V (285.38%)0.0 V3248.14 V (470.74%)1449515.6 WDrop High
6 mm²41 A32 A1312.75 V (190.25%)0.0 V2165.42 V (313.83%)966343.7 WDrop High
10 mm²57 A44 A787.65 V (114.15%)0.0 V1299.25 V (188.3%)579806.2 WDrop High
16 mm²76 A59 A492.28 V (71.35%)197.7 V812.03 V (117.69%)362378.9 WDrop High
25 mm²101 A78 A315.06 V (45.66%)374.9 V519.7 V (75.32%)231922.5 WDrop High
35 mm²125 A97 A225.04 V (32.61%)465.0 V371.22 V (53.8%)165658.9 WDrop High
50 mm²151 A118 A157.53 V (22.83%)532.5 V259.85 V (37.66%)115961.2 WDrop High
70 mm²192 A150 A112.52 V (16.31%)577.5 V185.61 V (26.9%)82829.5 WDrop High
95 mm²232 A181 A82.91 V (12.02%)607.1 V136.76 V (19.82%)61032.2 WDrop High
120 mm²269 A210 A65.64 V (9.51%)624.4 V108.27 V (15.69%)48317.2 WDrop High
150 mm²309 A241 A52.51 V (7.61%)637.5 V86.62 V (12.55%)38653.8 WDrop High
185 mm²353 A275 A42.58 V (6.17%)647.4 V70.23 V (10.18%)31340.9 WDrop High
240 mm²415 A324 A32.82 V (4.76%)657.2 V54.14 V (7.85%)24158.6 WDrop High
300 mm²477 A372 A26.26 V (3.81%)663.7 V43.31 V (6.28%)19326.9 W~ ≤5%
400 mm²570 A445 A19.69 V (2.85%)670.3 V32.48 V (4.71%)14495.2 W✓ OK (≤3%)

FAQ — 425 Amp Cable Size at 500 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 425A at 500 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 400 mm² copper cable for 425A over 500m at 690V (voltage drop: 19.69V or 2.85%).

What is the power capacity of 425A at 690V?

At unity power factor, 425A at 690V supports 507.92 kW with a standard 450A circuit breaker.