⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

425 Amp Cable Size at 600 Meters (230V Single-Phase (IEC Europe / UK / AU))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 425 A over 600 m (1968.5 ft).

Copper Cable (≤3% Drop)4× 400 mm²Drop: 6.82V (2.96%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 45.01V (19.57%)
Voltage at Load223.2 VLine Loss: 2899.0 W
Max Power & Breaker97.75 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 425A at 600m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A7276.0 V (3163.48%)0.0 V12002.0 V (5218.26%)3092300.0 WDrop High
2.5 mm²24 A18 A4365.6 V (1898.09%)0.0 V7201.2 V (3130.96%)1855380.0 WDrop High
4 mm²32 A25 A2728.5 V (1186.3%)0.0 V4500.75 V (1956.85%)1159612.5 WDrop High
6 mm²41 A32 A1819.0 V (790.87%)0.0 V3000.5 V (1304.57%)773075.0 WDrop High
10 mm²57 A44 A1091.4 V (474.52%)0.0 V1800.3 V (782.74%)463845.0 WDrop High
16 mm²76 A59 A682.12 V (296.58%)0.0 V1125.19 V (489.21%)289903.1 WDrop High
25 mm²101 A78 A436.56 V (189.81%)0.0 V720.12 V (313.1%)185538.0 WDrop High
35 mm²125 A97 A311.83 V (135.58%)0.0 V514.37 V (223.64%)132527.1 WDrop High
50 mm²151 A118 A218.28 V (94.9%)11.7 V360.06 V (156.55%)92769.0 WDrop High
70 mm²192 A150 A155.91 V (67.79%)74.1 V257.19 V (111.82%)66263.6 WDrop High
95 mm²232 A181 A114.88 V (49.95%)115.1 V189.51 V (82.39%)48825.8 WDrop High
120 mm²269 A210 A90.95 V (39.54%)139.1 V150.03 V (65.23%)38653.8 WDrop High
150 mm²309 A241 A72.76 V (31.63%)157.2 V120.02 V (52.18%)30923.0 WDrop High
185 mm²353 A275 A58.99 V (25.65%)171.0 V97.31 V (42.31%)25072.7 WDrop High
240 mm²415 A324 A45.48 V (19.77%)184.5 V75.01 V (32.61%)19326.9 WDrop High
300 mm²477 A372 A36.38 V (15.82%)193.6 V60.01 V (26.09%)15461.5 WDrop High
400 mm²570 A445 A27.28 V (11.86%)202.7 V45.01 V (19.57%)11596.1 WDrop High

FAQ — 425 Amp Cable Size at 600 Meters (230V Single-Phase (IEC Europe / UK / AU))

What mm² cable size is required for 425A at 600 meters (230V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 4× 400 mm² copper cable for 425A over 600m at 230V (voltage drop: 6.82V or 2.96%).

What is the power capacity of 425A at 230V?

At unity power factor, 425A at 230V supports 97.75 kW with a standard 450A circuit breaker.