⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

45 Amp Cable Size at 120 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 45 A over 120 m (393.7 ft).

Copper Cable (≤3% Drop)25 mm²Drop: 8.01V (1.93%)
Aluminum Cable (≤3% Drop)35 mm²Drop: 9.43V (2.27%)
Voltage at Load407.0 VLine Loss: 624.0 W
Max Power & Breaker32.35 kW45A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 45A at 120m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A133.44 V (32.15%)281.6 V220.11 V (53.04%)10400.4 WDrop High
2.5 mm²24 A18 A80.06 V (19.29%)334.9 V132.07 V (31.82%)6240.2 WDrop High
4 mm²32 A25 A50.04 V (12.06%)365.0 V82.54 V (19.89%)3900.2 WDrop High
6 mm²41 A32 A33.36 V (8.04%)381.6 V55.03 V (13.26%)2600.1 WDrop High
10 mm²57 A44 A20.02 V (4.82%)395.0 V33.02 V (7.96%)1560.1 W~ ≤5%
16 mm²76 A59 A12.51 V (3.01%)402.5 V20.64 V (4.97%)975.0 W~ ≤5%
25 mm²101 A78 A8.01 V (1.93%)407.0 V13.21 V (3.18%)624.0 W✓ OK (≤3%)
35 mm²125 A97 A5.72 V (1.38%)409.3 V9.43 V (2.27%)445.7 W✓ OK (≤3%)
50 mm²151 A118 A4.0 V (0.96%)411.0 V6.6 V (1.59%)312.0 W✓ OK (≤3%)
70 mm²192 A150 A2.86 V (0.69%)412.1 V4.72 V (1.14%)222.9 W✓ OK (≤3%)
95 mm²232 A181 A2.11 V (0.51%)412.9 V3.48 V (0.84%)164.2 W✓ OK (≤3%)
120 mm²269 A210 A1.67 V (0.4%)413.3 V2.75 V (0.66%)130.0 W✓ OK (≤3%)
150 mm²309 A241 A1.33 V (0.32%)413.7 V2.2 V (0.53%)104.0 W✓ OK (≤3%)
185 mm²353 A275 A1.08 V (0.26%)413.9 V1.78 V (0.43%)84.3 W✓ OK (≤3%)
240 mm²415 A324 A0.83 V (0.2%)414.2 V1.38 V (0.33%)65.0 W✓ OK (≤3%)
300 mm²477 A372 A0.67 V (0.16%)414.3 V1.1 V (0.27%)52.0 W✓ OK (≤3%)
400 mm²570 A445 A0.5 V (0.12%)414.5 V0.83 V (0.2%)39.0 W✓ OK (≤3%)

FAQ — 45 Amp Cable Size at 120 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 45A at 120 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 25 mm² copper cable for 45A over 120m at 415V (voltage drop: 8.01V or 1.93%).

What is the power capacity of 45A at 415V?

At unity power factor, 45A at 415V supports 32.35 kW with a standard 45A circuit breaker.