45 Amp Cable Size at 45 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 45 A over 45 m (147.6 ft).

Copper Cable (≤3% Drop)10 mm²Drop: 7.51V (1.81%)
Aluminum Cable (≤3% Drop)16 mm²Drop: 7.74V (1.86%)
Voltage at Load407.5 VLine Loss: 585.0 W
Max Power & Breaker32.35 kW45A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 45A at 45m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A50.04 V (12.06%)365.0 V82.54 V (19.89%)3900.2 WDrop High
2.5 mm²24 A18 A30.02 V (7.23%)385.0 V49.52 V (11.93%)2340.1 WDrop High
4 mm²32 A25 A18.76 V (4.52%)396.2 V30.95 V (7.46%)1462.6 WDrop High
6 mm²41 A32 A12.51 V (3.01%)402.5 V20.64 V (4.97%)975.0 WDrop High
10 mm²57 A44 A7.51 V (1.81%)407.5 V12.38 V (2.98%)585.0 W✓ OK (≤3%)
16 mm²76 A59 A4.69 V (1.13%)410.3 V7.74 V (1.86%)365.6 W✓ OK (≤3%)
25 mm²101 A78 A3.0 V (0.72%)412.0 V4.95 V (1.19%)234.0 W✓ OK (≤3%)
35 mm²125 A97 A2.14 V (0.52%)412.9 V3.54 V (0.85%)167.1 W✓ OK (≤3%)
50 mm²151 A118 A1.5 V (0.36%)413.5 V2.48 V (0.6%)117.0 W✓ OK (≤3%)
70 mm²192 A150 A1.07 V (0.26%)413.9 V1.77 V (0.43%)83.6 W✓ OK (≤3%)
95 mm²232 A181 A0.79 V (0.19%)414.2 V1.3 V (0.31%)61.6 W✓ OK (≤3%)
120 mm²269 A210 A0.63 V (0.15%)414.4 V1.03 V (0.25%)48.8 W✓ OK (≤3%)
150 mm²309 A241 A0.5 V (0.12%)414.5 V0.83 V (0.2%)39.0 W✓ OK (≤3%)
185 mm²353 A275 A0.41 V (0.1%)414.6 V0.67 V (0.16%)31.6 W✓ OK (≤3%)
240 mm²415 A324 A0.31 V (0.08%)414.7 V0.52 V (0.12%)24.4 W✓ OK (≤3%)
300 mm²477 A372 A0.25 V (0.06%)414.7 V0.41 V (0.1%)19.5 W✓ OK (≤3%)
400 mm²570 A445 A0.19 V (0.05%)414.8 V0.31 V (0.07%)14.6 W✓ OK (≤3%)

FAQ — 45 Amp Cable Size at 45 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 45A at 45 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 10 mm² copper cable for 45A over 45m at 415V (voltage drop: 7.51V or 1.81%).

What is the power capacity of 45A at 415V?

At unity power factor, 45A at 415V supports 32.35 kW with a standard 45A circuit breaker.