45 Amp Cable Size at 50 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 45 A over 50 m (164.0 ft).

Copper Cable (≤3% Drop)10 mm²Drop: 8.34V (2.01%)
Aluminum Cable (≤3% Drop)16 mm²Drop: 8.6V (2.07%)
Voltage at Load406.7 VLine Loss: 650.0 W
Max Power & Breaker32.35 kW45A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 45A at 50m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A55.6 V (13.4%)359.4 V91.71 V (22.1%)4333.5 WDrop High
2.5 mm²24 A18 A33.36 V (8.04%)381.6 V55.03 V (13.26%)2600.1 WDrop High
4 mm²32 A25 A20.85 V (5.02%)394.2 V34.39 V (8.29%)1625.1 WDrop High
6 mm²41 A32 A13.9 V (3.35%)401.1 V22.93 V (5.52%)1083.4 WDrop High
10 mm²57 A44 A8.34 V (2.01%)406.7 V13.76 V (3.31%)650.0 W✓ OK (≤3%)
16 mm²76 A59 A5.21 V (1.26%)409.8 V8.6 V (2.07%)406.3 W✓ OK (≤3%)
25 mm²101 A78 A3.34 V (0.8%)411.7 V5.5 V (1.33%)260.0 W✓ OK (≤3%)
35 mm²125 A97 A2.38 V (0.57%)412.6 V3.93 V (0.95%)185.7 W✓ OK (≤3%)
50 mm²151 A118 A1.67 V (0.4%)413.3 V2.75 V (0.66%)130.0 W✓ OK (≤3%)
70 mm²192 A150 A1.19 V (0.29%)413.8 V1.97 V (0.47%)92.9 W✓ OK (≤3%)
95 mm²232 A181 A0.88 V (0.21%)414.1 V1.45 V (0.35%)68.4 W✓ OK (≤3%)
120 mm²269 A210 A0.69 V (0.17%)414.3 V1.15 V (0.28%)54.2 W✓ OK (≤3%)
150 mm²309 A241 A0.56 V (0.13%)414.4 V0.92 V (0.22%)43.3 W✓ OK (≤3%)
185 mm²353 A275 A0.45 V (0.11%)414.5 V0.74 V (0.18%)35.1 W✓ OK (≤3%)
240 mm²415 A324 A0.35 V (0.08%)414.7 V0.57 V (0.14%)27.1 W✓ OK (≤3%)
300 mm²477 A372 A0.28 V (0.07%)414.7 V0.46 V (0.11%)21.7 W✓ OK (≤3%)
400 mm²570 A445 A0.21 V (0.05%)414.8 V0.34 V (0.08%)16.3 W✓ OK (≤3%)

FAQ — 45 Amp Cable Size at 50 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 45A at 50 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 10 mm² copper cable for 45A over 50m at 415V (voltage drop: 8.34V or 2.01%).

What is the power capacity of 45A at 415V?

At unity power factor, 45A at 415V supports 32.35 kW with a standard 45A circuit breaker.