45 Amp Cable Size at 50 Meters (230V Single-Phase (IEC Europe / UK / AU))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 45 A over 50 m (164.0 ft).

Copper Cable (≤3% Drop)16 mm²Drop: 6.02V (2.62%)
Aluminum Cable (≤3% Drop)25 mm²Drop: 6.35V (2.76%)
Voltage at Load224.0 VLine Loss: 270.8 W
Max Power & Breaker10.35 kW45A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 45A at 50m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A64.2 V (27.91%)165.8 V105.9 V (46.04%)2889.0 WDrop High
2.5 mm²24 A18 A38.52 V (16.75%)191.5 V63.54 V (27.63%)1733.4 WDrop High
4 mm²32 A25 A24.07 V (10.47%)205.9 V39.71 V (17.27%)1083.4 WDrop High
6 mm²41 A32 A16.05 V (6.98%)213.9 V26.47 V (11.51%)722.2 WDrop High
10 mm²57 A44 A9.63 V (4.19%)220.4 V15.88 V (6.91%)433.3 W~ ≤5%
16 mm²76 A59 A6.02 V (2.62%)224.0 V9.93 V (4.32%)270.8 W✓ OK (≤3%)
25 mm²101 A78 A3.85 V (1.67%)226.1 V6.35 V (2.76%)173.3 W✓ OK (≤3%)
35 mm²125 A97 A2.75 V (1.2%)227.2 V4.54 V (1.97%)123.8 W✓ OK (≤3%)
50 mm²151 A118 A1.93 V (0.84%)228.1 V3.18 V (1.38%)86.7 W✓ OK (≤3%)
70 mm²192 A150 A1.38 V (0.6%)228.6 V2.27 V (0.99%)61.9 W✓ OK (≤3%)
95 mm²232 A181 A1.01 V (0.44%)229.0 V1.67 V (0.73%)45.6 W✓ OK (≤3%)
120 mm²269 A210 A0.8 V (0.35%)229.2 V1.32 V (0.58%)36.1 W✓ OK (≤3%)
150 mm²309 A241 A0.64 V (0.28%)229.4 V1.06 V (0.46%)28.9 W✓ OK (≤3%)
185 mm²353 A275 A0.52 V (0.23%)229.5 V0.86 V (0.37%)23.4 W✓ OK (≤3%)
240 mm²415 A324 A0.4 V (0.17%)229.6 V0.66 V (0.29%)18.1 W✓ OK (≤3%)
300 mm²477 A372 A0.32 V (0.14%)229.7 V0.53 V (0.23%)14.4 W✓ OK (≤3%)
400 mm²570 A445 A0.24 V (0.1%)229.8 V0.4 V (0.17%)10.8 W✓ OK (≤3%)

FAQ — 45 Amp Cable Size at 50 Meters (230V Single-Phase (IEC Europe / UK / AU))

What mm² cable size is required for 45A at 50 meters (230V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 16 mm² copper cable for 45A over 50m at 230V (voltage drop: 6.02V or 2.62%).

What is the power capacity of 45A at 230V?

At unity power factor, 45A at 230V supports 10.35 kW with a standard 45A circuit breaker.