45 Amp Cable Size at 60 Meters (230V Single-Phase (IEC Europe / UK / AU))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 45 A over 60 m (196.9 ft).

Copper Cable (≤3% Drop)25 mm²Drop: 4.62V (2.01%)
Aluminum Cable (≤3% Drop)35 mm²Drop: 5.45V (2.37%)
Voltage at Load225.4 VLine Loss: 208.0 W
Max Power & Breaker10.35 kW45A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 45A at 60m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A77.04 V (33.5%)153.0 V127.08 V (55.25%)3466.8 WDrop High
2.5 mm²24 A18 A46.22 V (20.1%)183.8 V76.25 V (33.15%)2080.1 WDrop High
4 mm²32 A25 A28.89 V (12.56%)201.1 V47.65 V (20.72%)1300.0 WDrop High
6 mm²41 A32 A19.26 V (8.37%)210.7 V31.77 V (13.81%)866.7 WDrop High
10 mm²57 A44 A11.56 V (5.02%)218.4 V19.06 V (8.29%)520.0 WDrop High
16 mm²76 A59 A7.22 V (3.14%)222.8 V11.91 V (5.18%)325.0 W~ ≤5%
25 mm²101 A78 A4.62 V (2.01%)225.4 V7.62 V (3.32%)208.0 W✓ OK (≤3%)
35 mm²125 A97 A3.3 V (1.44%)226.7 V5.45 V (2.37%)148.6 W✓ OK (≤3%)
50 mm²151 A118 A2.31 V (1.0%)227.7 V3.81 V (1.66%)104.0 W✓ OK (≤3%)
70 mm²192 A150 A1.65 V (0.72%)228.3 V2.72 V (1.18%)74.3 W✓ OK (≤3%)
95 mm²232 A181 A1.22 V (0.53%)228.8 V2.01 V (0.87%)54.7 W✓ OK (≤3%)
120 mm²269 A210 A0.96 V (0.42%)229.0 V1.59 V (0.69%)43.3 W✓ OK (≤3%)
150 mm²309 A241 A0.77 V (0.33%)229.2 V1.27 V (0.55%)34.7 W✓ OK (≤3%)
185 mm²353 A275 A0.62 V (0.27%)229.4 V1.03 V (0.45%)28.1 W✓ OK (≤3%)
240 mm²415 A324 A0.48 V (0.21%)229.5 V0.79 V (0.35%)21.7 W✓ OK (≤3%)
300 mm²477 A372 A0.39 V (0.17%)229.6 V0.64 V (0.28%)17.3 W✓ OK (≤3%)
400 mm²570 A445 A0.29 V (0.13%)229.7 V0.48 V (0.21%)13.0 W✓ OK (≤3%)

FAQ — 45 Amp Cable Size at 60 Meters (230V Single-Phase (IEC Europe / UK / AU))

What mm² cable size is required for 45A at 60 meters (230V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 25 mm² copper cable for 45A over 60m at 230V (voltage drop: 4.62V or 2.01%).

What is the power capacity of 45A at 230V?

At unity power factor, 45A at 230V supports 10.35 kW with a standard 45A circuit breaker.