45 Amp Cable Size at 40 Meters (230V Single-Phase (IEC Europe / UK / AU))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 45 A over 40 m (131.2 ft).

Copper Cable (≤3% Drop)16 mm²Drop: 4.81V (2.09%)
Aluminum Cable (≤3% Drop)25 mm²Drop: 5.08V (2.21%)
Voltage at Load225.2 VLine Loss: 216.7 W
Max Power & Breaker10.35 kW45A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 45A at 40m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A51.36 V (22.33%)178.6 V84.72 V (36.83%)2311.2 WDrop High
2.5 mm²24 A18 A30.82 V (13.4%)199.2 V50.83 V (22.1%)1386.7 WDrop High
4 mm²32 A25 A19.26 V (8.37%)210.7 V31.77 V (13.81%)866.7 WDrop High
6 mm²41 A32 A12.84 V (5.58%)217.2 V21.18 V (9.21%)577.8 WDrop High
10 mm²57 A44 A7.7 V (3.35%)222.3 V12.71 V (5.53%)346.7 W~ ≤5%
16 mm²76 A59 A4.81 V (2.09%)225.2 V7.94 V (3.45%)216.7 W✓ OK (≤3%)
25 mm²101 A78 A3.08 V (1.34%)226.9 V5.08 V (2.21%)138.7 W✓ OK (≤3%)
35 mm²125 A97 A2.2 V (0.96%)227.8 V3.63 V (1.58%)99.1 W✓ OK (≤3%)
50 mm²151 A118 A1.54 V (0.67%)228.5 V2.54 V (1.11%)69.3 W✓ OK (≤3%)
70 mm²192 A150 A1.1 V (0.48%)228.9 V1.82 V (0.79%)49.5 W✓ OK (≤3%)
95 mm²232 A181 A0.81 V (0.35%)229.2 V1.34 V (0.58%)36.5 W✓ OK (≤3%)
120 mm²269 A210 A0.64 V (0.28%)229.4 V1.06 V (0.46%)28.9 W✓ OK (≤3%)
150 mm²309 A241 A0.51 V (0.22%)229.5 V0.85 V (0.37%)23.1 W✓ OK (≤3%)
185 mm²353 A275 A0.42 V (0.18%)229.6 V0.69 V (0.3%)18.7 W✓ OK (≤3%)
240 mm²415 A324 A0.32 V (0.14%)229.7 V0.53 V (0.23%)14.4 W✓ OK (≤3%)
300 mm²477 A372 A0.26 V (0.11%)229.7 V0.42 V (0.18%)11.6 W✓ OK (≤3%)
400 mm²570 A445 A0.19 V (0.08%)229.8 V0.32 V (0.14%)8.7 W✓ OK (≤3%)

FAQ — 45 Amp Cable Size at 40 Meters (230V Single-Phase (IEC Europe / UK / AU))

What mm² cable size is required for 45A at 40 meters (230V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 16 mm² copper cable for 45A over 40m at 230V (voltage drop: 4.81V or 2.09%).

What is the power capacity of 45A at 230V?

At unity power factor, 45A at 230V supports 10.35 kW with a standard 45A circuit breaker.