45 Amp Cable Size at 5 Meters (230V Single-Phase (IEC Europe / UK / AU))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 45 A over 5 m (16.4 ft).

Copper Cable (≤3% Drop)10 mm²Drop: 0.96V (0.42%)
Aluminum Cable (≤3% Drop)16 mm²Drop: 0.99V (0.43%)
Voltage at Load229.0 VLine Loss: 43.3 W
Max Power & Breaker10.35 kW45A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 45A at 5m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A6.42 V (2.79%)223.6 V10.59 V (4.6%)288.9 WDrop High
2.5 mm²24 A18 A3.85 V (1.67%)226.1 V6.35 V (2.76%)173.3 WDrop High
4 mm²32 A25 A2.41 V (1.05%)227.6 V3.97 V (1.73%)108.3 WDrop High
6 mm²41 A32 A1.6 V (0.7%)228.4 V2.65 V (1.15%)72.2 WDrop High
10 mm²57 A44 A0.96 V (0.42%)229.0 V1.59 V (0.69%)43.3 W✓ OK (≤3%)
16 mm²76 A59 A0.6 V (0.26%)229.4 V0.99 V (0.43%)27.1 W✓ OK (≤3%)
25 mm²101 A78 A0.39 V (0.17%)229.6 V0.64 V (0.28%)17.3 W✓ OK (≤3%)
35 mm²125 A97 A0.28 V (0.12%)229.7 V0.45 V (0.2%)12.4 W✓ OK (≤3%)
50 mm²151 A118 A0.19 V (0.08%)229.8 V0.32 V (0.14%)8.7 W✓ OK (≤3%)
70 mm²192 A150 A0.14 V (0.06%)229.9 V0.23 V (0.1%)6.2 W✓ OK (≤3%)
95 mm²232 A181 A0.1 V (0.04%)229.9 V0.17 V (0.07%)4.6 W✓ OK (≤3%)
120 mm²269 A210 A0.08 V (0.03%)229.9 V0.13 V (0.06%)3.6 W✓ OK (≤3%)
150 mm²309 A241 A0.06 V (0.03%)229.9 V0.11 V (0.05%)2.9 W✓ OK (≤3%)
185 mm²353 A275 A0.05 V (0.02%)229.9 V0.09 V (0.04%)2.3 W✓ OK (≤3%)
240 mm²415 A324 A0.04 V (0.02%)230.0 V0.07 V (0.03%)1.8 W✓ OK (≤3%)
300 mm²477 A372 A0.03 V (0.01%)230.0 V0.05 V (0.02%)1.4 W✓ OK (≤3%)
400 mm²570 A445 A0.02 V (0.01%)230.0 V0.04 V (0.02%)1.1 W✓ OK (≤3%)

FAQ — 45 Amp Cable Size at 5 Meters (230V Single-Phase (IEC Europe / UK / AU))

What mm² cable size is required for 45A at 5 meters (230V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 10 mm² copper cable for 45A over 5m at 230V (voltage drop: 0.96V or 0.42%).

What is the power capacity of 45A at 230V?

At unity power factor, 45A at 230V supports 10.35 kW with a standard 45A circuit breaker.