45 Amp Cable Size at 600 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 45 A over 600 m (1968.5 ft).

Copper Cable (≤3% Drop)50 mm²Drop: 20.02V (2.9%)
Aluminum Cable (≤3% Drop)95 mm²Drop: 17.38V (2.52%)
Voltage at Load670.0 VLine Loss: 1560.1 W
Max Power & Breaker53.78 kW45A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 45A at 600m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A667.19 V (96.69%)22.8 V1100.55 V (159.5%)52002.0 WDrop High
2.5 mm²24 A18 A400.31 V (58.02%)289.7 V660.33 V (95.7%)31201.2 WDrop High
4 mm²32 A25 A250.19 V (36.26%)439.8 V412.7 V (59.81%)19500.8 WDrop High
6 mm²41 A32 A166.8 V (24.17%)523.2 V275.14 V (39.87%)13000.5 WDrop High
10 mm²57 A44 A100.08 V (14.5%)589.9 V165.08 V (23.92%)7800.3 WDrop High
16 mm²76 A59 A62.55 V (9.07%)627.5 V103.18 V (14.95%)4875.2 WDrop High
25 mm²101 A78 A40.03 V (5.8%)650.0 V66.03 V (9.57%)3120.1 WDrop High
35 mm²125 A97 A28.59 V (4.14%)661.4 V47.17 V (6.84%)2228.7 W~ ≤5%
50 mm²151 A118 A20.02 V (2.9%)670.0 V33.02 V (4.78%)1560.1 W✓ OK (≤3%)
70 mm²192 A150 A14.3 V (2.07%)675.7 V23.58 V (3.42%)1114.3 W✓ OK (≤3%)
95 mm²232 A181 A10.53 V (1.53%)679.5 V17.38 V (2.52%)821.1 W✓ OK (≤3%)
120 mm²269 A210 A8.34 V (1.21%)681.7 V13.76 V (1.99%)650.0 W✓ OK (≤3%)
150 mm²309 A241 A6.67 V (0.97%)683.3 V11.01 V (1.59%)520.0 W✓ OK (≤3%)
185 mm²353 A275 A5.41 V (0.78%)684.6 V8.92 V (1.29%)421.6 W✓ OK (≤3%)
240 mm²415 A324 A4.17 V (0.6%)685.8 V6.88 V (1.0%)325.0 W✓ OK (≤3%)
300 mm²477 A372 A3.34 V (0.48%)686.7 V5.5 V (0.8%)260.0 W✓ OK (≤3%)
400 mm²570 A445 A2.5 V (0.36%)687.5 V4.13 V (0.6%)195.0 W✓ OK (≤3%)

FAQ — 45 Amp Cable Size at 600 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 45A at 600 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 50 mm² copper cable for 45A over 600m at 690V (voltage drop: 20.02V or 2.9%).

What is the power capacity of 45A at 690V?

At unity power factor, 45A at 690V supports 53.78 kW with a standard 45A circuit breaker.