450 Amp Cable Size at 25 Meters (690V Three-Phase (Wind / Heavy Industrial))
IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 450 A over 25 m (82.0 ft).
Copper Cable (≤3% Drop)300 mm²Drop: 1.39V (0.2%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 1.72V (0.25%)
Voltage at Load688.6 VLine Loss: 1083.4 W
Max Power & Breaker537.8 kW450A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 450A at 25m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 277.99 V (40.29%) | 412.0 V | 458.56 V (66.46%) | 216675.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 166.8 V (24.17%) | 523.2 V | 275.14 V (39.87%) | 130005.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 104.25 V (15.11%) | 585.8 V | 171.96 V (24.92%) | 81253.1 W | Drop High |
| 6 mm² | 41 A | 32 A | 69.5 V (10.07%) | 620.5 V | 114.64 V (16.61%) | 54168.7 W | Drop High |
| 10 mm² | 57 A | 44 A | 41.7 V (6.04%) | 648.3 V | 68.78 V (9.97%) | 32501.2 W | Drop High |
| 16 mm² | 76 A | 59 A | 26.06 V (3.78%) | 663.9 V | 42.99 V (6.23%) | 20313.3 W | Drop High |
| 25 mm² | 101 A | 78 A | 16.68 V (2.42%) | 673.3 V | 27.51 V (3.99%) | 13000.5 W | Drop High |
| 35 mm² | 125 A | 97 A | 11.91 V (1.73%) | 678.1 V | 19.65 V (2.85%) | 9286.1 W | Drop High |
| 50 mm² | 151 A | 118 A | 8.34 V (1.21%) | 681.7 V | 13.76 V (1.99%) | 6500.2 W | Drop High |
| 70 mm² | 192 A | 150 A | 5.96 V (0.86%) | 684.0 V | 9.83 V (1.42%) | 4643.0 W | Drop High |
| 95 mm² | 232 A | 181 A | 4.39 V (0.64%) | 685.6 V | 7.24 V (1.05%) | 3421.2 W | Drop High |
| 120 mm² | 269 A | 210 A | 3.47 V (0.5%) | 686.5 V | 5.73 V (0.83%) | 2708.4 W | Drop High |
| 150 mm² | 309 A | 241 A | 2.78 V (0.4%) | 687.2 V | 4.59 V (0.66%) | 2166.8 W | Drop High |
| 185 mm² | 353 A | 275 A | 2.25 V (0.33%) | 687.7 V | 3.72 V (0.54%) | 1756.8 W | Drop High |
| 240 mm² | 415 A | 324 A | 1.74 V (0.25%) | 688.3 V | 2.87 V (0.42%) | 1354.2 W | Drop High |
| 300 mm² | 477 A | 372 A | 1.39 V (0.2%) | 688.6 V | 2.29 V (0.33%) | 1083.4 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 1.04 V (0.15%) | 689.0 V | 1.72 V (0.25%) | 812.5 W | ✓ OK (≤3%) |
FAQ — 450 Amp Cable Size at 25 Meters (690V Three-Phase (Wind / Heavy Industrial))
What mm² cable size is required for 450A at 25 meters (690V)?
According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 300 mm² copper cable for 450A over 25m at 690V (voltage drop: 1.39V or 0.2%).
What is the power capacity of 450A at 690V?
At unity power factor, 450A at 690V supports 537.8 kW with a standard 450A circuit breaker.
Related Lengths & Currents (690V)
450A · 5m (690V)450A · 10m (690V)450A · 15m (690V)450A · 20m (690V)450A · 30m (690V)450A · 35m (690V)450A · 40m (690V)450A · 45m (690V)450A · 50m (690V)450A · 60m (690V)450A · 70m (690V)10A · 25m (690V)16A · 25m (690V)20A · 25m (690V)25A · 25m (690V)32A · 25m (690V)40A · 25m (690V)50A · 25m (690V)63A · 25m (690V)80A · 25m (690V)100A · 25m (690V)125A · 25m (690V)160A · 25m (690V)200A · 25m (690V)