450 Amp Cable Size at 45 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 450 A over 45 m (147.6 ft).

Copper Cable (≤3% Drop)300 mm²Drop: 2.5V (0.36%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 3.1V (0.45%)
Voltage at Load687.5 VLine Loss: 1950.1 W
Max Power & Breaker537.8 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 450A at 45m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A500.39 V (72.52%)189.6 V825.41 V (119.62%)390015.0 WDrop High
2.5 mm²24 A18 A300.23 V (43.51%)389.8 V495.25 V (71.77%)234009.0 WDrop High
4 mm²32 A25 A187.65 V (27.2%)502.4 V309.53 V (44.86%)146255.6 WDrop High
6 mm²41 A32 A125.1 V (18.13%)564.9 V206.35 V (29.91%)97503.8 WDrop High
10 mm²57 A44 A75.06 V (10.88%)614.9 V123.81 V (17.94%)58502.2 WDrop High
16 mm²76 A59 A46.91 V (6.8%)643.1 V77.38 V (11.21%)36563.9 WDrop High
25 mm²101 A78 A30.02 V (4.35%)660.0 V49.52 V (7.18%)23400.9 WDrop High
35 mm²125 A97 A21.45 V (3.11%)668.6 V35.37 V (5.13%)16714.9 WDrop High
50 mm²151 A118 A15.01 V (2.18%)675.0 V24.76 V (3.59%)11700.4 WDrop High
70 mm²192 A150 A10.72 V (1.55%)679.3 V17.69 V (2.56%)8357.5 WDrop High
95 mm²232 A181 A7.9 V (1.15%)682.1 V13.03 V (1.89%)6158.1 WDrop High
120 mm²269 A210 A6.25 V (0.91%)683.7 V10.32 V (1.5%)4875.2 WDrop High
150 mm²309 A241 A5.0 V (0.73%)685.0 V8.25 V (1.2%)3900.1 WDrop High
185 mm²353 A275 A4.06 V (0.59%)685.9 V6.69 V (0.97%)3162.3 WDrop High
240 mm²415 A324 A3.13 V (0.45%)686.9 V5.16 V (0.75%)2437.6 WDrop High
300 mm²477 A372 A2.5 V (0.36%)687.5 V4.13 V (0.6%)1950.1 W✓ OK (≤3%)
400 mm²570 A445 A1.88 V (0.27%)688.1 V3.1 V (0.45%)1462.6 W✓ OK (≤3%)

FAQ — 450 Amp Cable Size at 45 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 450A at 45 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 300 mm² copper cable for 450A over 45m at 690V (voltage drop: 2.5V or 0.36%).

What is the power capacity of 450A at 690V?

At unity power factor, 450A at 690V supports 537.8 kW with a standard 450A circuit breaker.