⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

450 Amp Cable Size at 5 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 450 A over 5 m (16.4 ft).

Copper Cable (≤3% Drop)300 mm²Drop: 0.28V (0.04%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 0.34V (0.05%)
Voltage at Load689.7 VLine Loss: 216.7 W
Max Power & Breaker537.8 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 450A at 5m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A55.6 V (8.06%)634.4 V91.71 V (13.29%)43335.0 WDrop High
2.5 mm²24 A18 A33.36 V (4.83%)656.6 V55.03 V (7.97%)26001.0 WDrop High
4 mm²32 A25 A20.85 V (3.02%)669.2 V34.39 V (4.98%)16250.6 WDrop High
6 mm²41 A32 A13.9 V (2.01%)676.1 V22.93 V (3.32%)10833.8 WDrop High
10 mm²57 A44 A8.34 V (1.21%)681.7 V13.76 V (1.99%)6500.2 WDrop High
16 mm²76 A59 A5.21 V (0.76%)684.8 V8.6 V (1.25%)4062.7 WDrop High
25 mm²101 A78 A3.34 V (0.48%)686.7 V5.5 V (0.8%)2600.1 WDrop High
35 mm²125 A97 A2.38 V (0.35%)687.6 V3.93 V (0.57%)1857.2 WDrop High
50 mm²151 A118 A1.67 V (0.24%)688.3 V2.75 V (0.4%)1300.0 WDrop High
70 mm²192 A150 A1.19 V (0.17%)688.8 V1.97 V (0.28%)928.6 WDrop High
95 mm²232 A181 A0.88 V (0.13%)689.1 V1.45 V (0.21%)684.2 WDrop High
120 mm²269 A210 A0.69 V (0.1%)689.3 V1.15 V (0.17%)541.7 WDrop High
150 mm²309 A241 A0.56 V (0.08%)689.4 V0.92 V (0.13%)433.3 WDrop High
185 mm²353 A275 A0.45 V (0.07%)689.5 V0.74 V (0.11%)351.4 WDrop High
240 mm²415 A324 A0.35 V (0.05%)689.7 V0.57 V (0.08%)270.8 WDrop High
300 mm²477 A372 A0.28 V (0.04%)689.7 V0.46 V (0.07%)216.7 W✓ OK (≤3%)
400 mm²570 A445 A0.21 V (0.03%)689.8 V0.34 V (0.05%)162.5 W✓ OK (≤3%)

FAQ — 450 Amp Cable Size at 5 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 450A at 5 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 300 mm² copper cable for 450A over 5m at 690V (voltage drop: 0.28V or 0.04%).

What is the power capacity of 450A at 690V?

At unity power factor, 450A at 690V supports 537.8 kW with a standard 450A circuit breaker.