450 Amp Cable Size at 45 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 450 A over 45 m (147.6 ft).

Copper Cable (≤3% Drop)300 mm²Drop: 2.5V (0.6%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 3.1V (0.75%)
Voltage at Load412.5 VLine Loss: 1950.1 W
Max Power & Breaker323.46 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 450A at 45m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A500.39 V (120.58%)0.0 V825.41 V (198.89%)390015.0 WDrop High
2.5 mm²24 A18 A300.23 V (72.35%)114.8 V495.25 V (119.34%)234009.0 WDrop High
4 mm²32 A25 A187.65 V (45.22%)227.4 V309.53 V (74.59%)146255.6 WDrop High
6 mm²41 A32 A125.1 V (30.14%)289.9 V206.35 V (49.72%)97503.8 WDrop High
10 mm²57 A44 A75.06 V (18.09%)339.9 V123.81 V (29.83%)58502.2 WDrop High
16 mm²76 A59 A46.91 V (11.3%)368.1 V77.38 V (18.65%)36563.9 WDrop High
25 mm²101 A78 A30.02 V (7.23%)385.0 V49.52 V (11.93%)23400.9 WDrop High
35 mm²125 A97 A21.45 V (5.17%)393.6 V35.37 V (8.52%)16714.9 WDrop High
50 mm²151 A118 A15.01 V (3.62%)400.0 V24.76 V (5.97%)11700.4 WDrop High
70 mm²192 A150 A10.72 V (2.58%)404.3 V17.69 V (4.26%)8357.5 WDrop High
95 mm²232 A181 A7.9 V (1.9%)407.1 V13.03 V (3.14%)6158.1 WDrop High
120 mm²269 A210 A6.25 V (1.51%)408.7 V10.32 V (2.49%)4875.2 WDrop High
150 mm²309 A241 A5.0 V (1.21%)410.0 V8.25 V (1.99%)3900.1 WDrop High
185 mm²353 A275 A4.06 V (0.98%)410.9 V6.69 V (1.61%)3162.3 WDrop High
240 mm²415 A324 A3.13 V (0.75%)411.9 V5.16 V (1.24%)2437.6 WDrop High
300 mm²477 A372 A2.5 V (0.6%)412.5 V4.13 V (0.99%)1950.1 W✓ OK (≤3%)
400 mm²570 A445 A1.88 V (0.45%)413.1 V3.1 V (0.75%)1462.6 W✓ OK (≤3%)

FAQ — 450 Amp Cable Size at 45 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 450A at 45 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 300 mm² copper cable for 450A over 45m at 415V (voltage drop: 2.5V or 0.6%).

What is the power capacity of 450A at 415V?

At unity power factor, 450A at 415V supports 323.46 kW with a standard 450A circuit breaker.