450 Amp Cable Size at 50 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 450 A over 50 m (164.0 ft).

Copper Cable (≤3% Drop)300 mm²Drop: 2.78V (0.67%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 3.44V (0.83%)
Voltage at Load412.2 VLine Loss: 2166.8 W
Max Power & Breaker323.46 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 450A at 50m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A555.99 V (133.97%)0.0 V917.12 V (220.99%)433350.0 WDrop High
2.5 mm²24 A18 A333.59 V (80.38%)81.4 V550.27 V (132.6%)260010.0 WDrop High
4 mm²32 A25 A208.5 V (50.24%)206.5 V343.92 V (82.87%)162506.2 WDrop High
6 mm²41 A32 A139.0 V (33.49%)276.0 V229.28 V (55.25%)108337.5 WDrop High
10 mm²57 A44 A83.4 V (20.1%)331.6 V137.57 V (33.15%)65002.5 WDrop High
16 mm²76 A59 A52.12 V (12.56%)362.9 V85.98 V (20.72%)40626.6 WDrop High
25 mm²101 A78 A33.36 V (8.04%)381.6 V55.03 V (13.26%)26001.0 WDrop High
35 mm²125 A97 A23.83 V (5.74%)391.2 V39.31 V (9.47%)18572.1 WDrop High
50 mm²151 A118 A16.68 V (4.02%)398.3 V27.51 V (6.63%)13000.5 WDrop High
70 mm²192 A150 A11.91 V (2.87%)403.1 V19.65 V (4.74%)9286.1 WDrop High
95 mm²232 A181 A8.78 V (2.12%)406.2 V14.48 V (3.49%)6842.4 WDrop High
120 mm²269 A210 A6.95 V (1.67%)408.1 V11.46 V (2.76%)5416.9 WDrop High
150 mm²309 A241 A5.56 V (1.34%)409.4 V9.17 V (2.21%)4333.5 WDrop High
185 mm²353 A275 A4.51 V (1.09%)410.5 V7.44 V (1.79%)3513.6 WDrop High
240 mm²415 A324 A3.47 V (0.84%)411.5 V5.73 V (1.38%)2708.4 WDrop High
300 mm²477 A372 A2.78 V (0.67%)412.2 V4.59 V (1.1%)2166.8 W✓ OK (≤3%)
400 mm²570 A445 A2.08 V (0.5%)412.9 V3.44 V (0.83%)1625.1 W✓ OK (≤3%)

FAQ — 450 Amp Cable Size at 50 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 450A at 50 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 300 mm² copper cable for 450A over 50m at 415V (voltage drop: 2.78V or 0.67%).

What is the power capacity of 450A at 415V?

At unity power factor, 450A at 415V supports 323.46 kW with a standard 450A circuit breaker.