475 Amp Cable Size at 250 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 475 A over 250 m (820.2 ft).

Copper Cable (≤3% Drop)400 mm²Drop: 11.0V (2.65%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 18.15V (4.37%)
Voltage at Load404.0 VLine Loss: 9053.2 W
Max Power & Breaker341.43 kW500A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 475A at 250m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A2934.38 V (707.08%)0.0 V4840.36 V (1166.35%)2414187.5 WDrop High
2.5 mm²24 A18 A1760.63 V (424.25%)0.0 V2904.22 V (699.81%)1448512.5 WDrop High
4 mm²32 A25 A1100.39 V (265.16%)0.0 V1815.14 V (437.38%)905320.3 WDrop High
6 mm²41 A32 A733.6 V (176.77%)0.0 V1210.09 V (291.59%)603546.9 WDrop High
10 mm²57 A44 A440.16 V (106.06%)0.0 V726.05 V (174.95%)362128.1 WDrop High
16 mm²76 A59 A275.1 V (66.29%)139.9 V453.78 V (109.35%)226330.1 WDrop High
25 mm²101 A78 A176.06 V (42.42%)238.9 V290.42 V (69.98%)144851.2 WDrop High
35 mm²125 A97 A125.76 V (30.3%)289.2 V207.44 V (49.99%)103465.2 WDrop High
50 mm²151 A118 A88.03 V (21.21%)327.0 V145.21 V (34.99%)72425.6 WDrop High
70 mm²192 A150 A62.88 V (15.15%)352.1 V103.72 V (24.99%)51732.6 WDrop High
95 mm²232 A181 A46.33 V (11.16%)368.7 V76.43 V (18.42%)38118.8 WDrop High
120 mm²269 A210 A36.68 V (8.84%)378.3 V60.5 V (14.58%)30177.3 WDrop High
150 mm²309 A241 A29.34 V (7.07%)385.7 V48.4 V (11.66%)24141.9 WDrop High
185 mm²353 A275 A23.79 V (5.73%)391.2 V39.25 V (9.46%)19574.5 WDrop High
240 mm²415 A324 A18.34 V (4.42%)396.7 V30.25 V (7.29%)15088.7 WDrop High
300 mm²477 A372 A14.67 V (3.54%)400.3 V24.2 V (5.83%)12070.9 W~ ≤5%
400 mm²570 A445 A11.0 V (2.65%)404.0 V18.15 V (4.37%)9053.2 W✓ OK (≤3%)

FAQ — 475 Amp Cable Size at 250 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 475A at 250 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 400 mm² copper cable for 475A over 250m at 415V (voltage drop: 11.0V or 2.65%).

What is the power capacity of 475A at 415V?

At unity power factor, 475A at 415V supports 341.43 kW with a standard 500A circuit breaker.