475 Amp Cable Size at 300 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 475 A over 300 m (984.3 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 6.6V (1.59%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 21.78V (5.25%)
Voltage at Load408.4 VLine Loss: 5431.9 W
Max Power & Breaker341.43 kW500A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 475A at 300m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A3521.26 V (848.5%)0.0 V5808.43 V (1399.62%)2897025.0 WDrop High
2.5 mm²24 A18 A2112.76 V (509.1%)0.0 V3485.06 V (839.77%)1738215.0 WDrop High
4 mm²32 A25 A1320.47 V (318.19%)0.0 V2178.16 V (524.86%)1086384.4 WDrop High
6 mm²41 A32 A880.31 V (212.12%)0.0 V1452.11 V (349.91%)724256.2 WDrop High
10 mm²57 A44 A528.19 V (127.27%)0.0 V871.26 V (209.94%)434553.8 WDrop High
16 mm²76 A59 A330.12 V (79.55%)84.9 V544.54 V (131.21%)271596.1 WDrop High
25 mm²101 A78 A211.28 V (50.91%)203.7 V348.51 V (83.98%)173821.5 WDrop High
35 mm²125 A97 A150.91 V (36.36%)264.1 V248.93 V (59.98%)124158.2 WDrop High
50 mm²151 A118 A105.64 V (25.45%)309.4 V174.25 V (41.99%)86910.7 WDrop High
70 mm²192 A150 A75.46 V (18.18%)339.5 V124.47 V (29.99%)62079.1 WDrop High
95 mm²232 A181 A55.6 V (13.4%)359.4 V91.71 V (22.1%)45742.5 WDrop High
120 mm²269 A210 A44.02 V (10.61%)371.0 V72.61 V (17.5%)36212.8 WDrop High
150 mm²309 A241 A35.21 V (8.48%)379.8 V58.08 V (14.0%)28970.2 WDrop High
185 mm²353 A275 A28.55 V (6.88%)386.4 V47.1 V (11.35%)23489.4 WDrop High
240 mm²415 A324 A22.01 V (5.3%)393.0 V36.3 V (8.75%)18106.4 WDrop High
300 mm²477 A372 A17.61 V (4.24%)397.4 V29.04 V (7.0%)14485.1 W~ ≤5%
400 mm²570 A445 A13.2 V (3.18%)401.8 V21.78 V (5.25%)10863.8 W~ ≤5%

FAQ — 475 Amp Cable Size at 300 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 475A at 300 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 475A over 300m at 415V (voltage drop: 6.6V or 1.59%).

What is the power capacity of 475A at 415V?

At unity power factor, 475A at 415V supports 341.43 kW with a standard 500A circuit breaker.