⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

475 Amp Cable Size at 80 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 475 A over 80 m (262.5 ft).

Copper Cable (≤3% Drop)300 mm²Drop: 4.7V (0.68%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 5.81V (0.84%)
Voltage at Load685.3 VLine Loss: 3862.7 W
Max Power & Breaker567.68 kW500A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 475A at 80m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A939.0 V (136.09%)0.0 V1548.92 V (224.48%)772540.0 WDrop High
2.5 mm²24 A18 A563.4 V (81.65%)126.6 V929.35 V (134.69%)463524.0 WDrop High
4 mm²32 A25 A352.13 V (51.03%)337.9 V580.84 V (84.18%)289702.5 WDrop High
6 mm²41 A32 A234.75 V (34.02%)455.2 V387.23 V (56.12%)193135.0 WDrop High
10 mm²57 A44 A140.85 V (20.41%)549.1 V232.34 V (33.67%)115881.0 WDrop High
16 mm²76 A59 A88.03 V (12.76%)602.0 V145.21 V (21.05%)72425.6 WDrop High
25 mm²101 A78 A56.34 V (8.17%)633.7 V92.93 V (13.47%)46352.4 WDrop High
35 mm²125 A97 A40.24 V (5.83%)649.8 V66.38 V (9.62%)33108.9 WDrop High
50 mm²151 A118 A28.17 V (4.08%)661.8 V46.47 V (6.73%)23176.2 WDrop High
70 mm²192 A150 A20.12 V (2.92%)669.9 V33.19 V (4.81%)16554.4 WDrop High
95 mm²232 A181 A14.83 V (2.15%)675.2 V24.46 V (3.54%)12198.0 WDrop High
120 mm²269 A210 A11.74 V (1.7%)678.3 V19.36 V (2.81%)9656.8 WDrop High
150 mm²309 A241 A9.39 V (1.36%)680.6 V15.49 V (2.24%)7725.4 WDrop High
185 mm²353 A275 A7.61 V (1.1%)682.4 V12.56 V (1.82%)6263.8 WDrop High
240 mm²415 A324 A5.87 V (0.85%)684.1 V9.68 V (1.4%)4828.4 WDrop High
300 mm²477 A372 A4.7 V (0.68%)685.3 V7.74 V (1.12%)3862.7 W✓ OK (≤3%)
400 mm²570 A445 A3.52 V (0.51%)686.5 V5.81 V (0.84%)2897.0 W✓ OK (≤3%)

FAQ — 475 Amp Cable Size at 80 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 475A at 80 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 300 mm² copper cable for 475A over 80m at 690V (voltage drop: 4.7V or 0.68%).

What is the power capacity of 475A at 690V?

At unity power factor, 475A at 690V supports 567.68 kW with a standard 500A circuit breaker.