5 Amp Cable Size at 30 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 5 A over 30 m (98.4 ft).

Copper Cable (≤3% Drop)6 mm²Drop: 1.07V (2.23%)
Aluminum Cable (≤3% Drop)10 mm²Drop: 1.06V (2.21%)
Voltage at Load46.9 VLine Loss: 5.3 W
Max Power & Breaker0.24 kW6A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 5A at 30m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A4.28 V (8.92%)43.7 V7.06 V (14.71%)21.4 WDrop High
2.5 mm²24 A18 A2.57 V (5.35%)45.4 V4.24 V (8.82%)12.8 WDrop High
4 mm²32 A25 A1.6 V (3.34%)46.4 V2.65 V (5.52%)8.0 W~ ≤5%
6 mm²41 A32 A1.07 V (2.23%)46.9 V1.76 V (3.68%)5.3 W✓ OK (≤3%)
10 mm²57 A44 A0.64 V (1.34%)47.4 V1.06 V (2.21%)3.2 W✓ OK (≤3%)
16 mm²76 A59 A0.4 V (0.84%)47.6 V0.66 V (1.38%)2.0 W✓ OK (≤3%)
25 mm²101 A78 A0.26 V (0.54%)47.7 V0.42 V (0.88%)1.3 W✓ OK (≤3%)
35 mm²125 A97 A0.18 V (0.38%)47.8 V0.3 V (0.63%)0.9 W✓ OK (≤3%)
50 mm²151 A118 A0.13 V (0.27%)47.9 V0.21 V (0.44%)0.6 W✓ OK (≤3%)
70 mm²192 A150 A0.09 V (0.19%)47.9 V0.15 V (0.32%)0.5 W✓ OK (≤3%)
95 mm²232 A181 A0.07 V (0.14%)47.9 V0.11 V (0.23%)0.3 W✓ OK (≤3%)
120 mm²269 A210 A0.05 V (0.11%)47.9 V0.09 V (0.18%)0.3 W✓ OK (≤3%)
150 mm²309 A241 A0.04 V (0.09%)48.0 V0.07 V (0.15%)0.2 W✓ OK (≤3%)
185 mm²353 A275 A0.03 V (0.07%)48.0 V0.06 V (0.12%)0.2 W✓ OK (≤3%)
240 mm²415 A324 A0.03 V (0.06%)48.0 V0.04 V (0.09%)0.1 W✓ OK (≤3%)
300 mm²477 A372 A0.02 V (0.04%)48.0 V0.04 V (0.07%)0.1 W✓ OK (≤3%)
400 mm²570 A445 A0.02 V (0.03%)48.0 V0.03 V (0.06%)0.1 W✓ OK (≤3%)

FAQ — 5 Amp Cable Size at 30 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 5A at 30 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 6 mm² copper cable for 5A over 30m at 48V (voltage drop: 1.07V or 2.23%).

What is the power capacity of 5A at 48V?

At unity power factor, 5A at 48V supports 0.24 kW with a standard 6A circuit breaker.