5 Amp Cable Size at 25 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 5 A over 25 m (82.0 ft).

Copper Cable (≤3% Drop)4 mm²Drop: 1.34V (2.79%)
Aluminum Cable (≤3% Drop)10 mm²Drop: 0.88V (1.84%)
Voltage at Load46.7 VLine Loss: 6.7 W
Max Power & Breaker0.24 kW6A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 5A at 25m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A3.57 V (7.43%)44.4 V5.88 V (12.26%)17.8 WDrop High
2.5 mm²24 A18 A2.14 V (4.46%)45.9 V3.53 V (7.35%)10.7 W~ ≤5%
4 mm²32 A25 A1.34 V (2.79%)46.7 V2.21 V (4.6%)6.7 W✓ OK (≤3%)
6 mm²41 A32 A0.89 V (1.86%)47.1 V1.47 V (3.06%)4.5 W✓ OK (≤3%)
10 mm²57 A44 A0.53 V (1.11%)47.5 V0.88 V (1.84%)2.7 W✓ OK (≤3%)
16 mm²76 A59 A0.33 V (0.7%)47.7 V0.55 V (1.15%)1.7 W✓ OK (≤3%)
25 mm²101 A78 A0.21 V (0.45%)47.8 V0.35 V (0.74%)1.1 W✓ OK (≤3%)
35 mm²125 A97 A0.15 V (0.32%)47.8 V0.25 V (0.53%)0.8 W✓ OK (≤3%)
50 mm²151 A118 A0.11 V (0.22%)47.9 V0.18 V (0.37%)0.5 W✓ OK (≤3%)
70 mm²192 A150 A0.08 V (0.16%)47.9 V0.13 V (0.26%)0.4 W✓ OK (≤3%)
95 mm²232 A181 A0.06 V (0.12%)47.9 V0.09 V (0.19%)0.3 W✓ OK (≤3%)
120 mm²269 A210 A0.04 V (0.09%)48.0 V0.07 V (0.15%)0.2 W✓ OK (≤3%)
150 mm²309 A241 A0.04 V (0.07%)48.0 V0.06 V (0.12%)0.2 W✓ OK (≤3%)
185 mm²353 A275 A0.03 V (0.06%)48.0 V0.05 V (0.1%)0.1 W✓ OK (≤3%)
240 mm²415 A324 A0.02 V (0.05%)48.0 V0.04 V (0.08%)0.1 W✓ OK (≤3%)
300 mm²477 A372 A0.02 V (0.04%)48.0 V0.03 V (0.06%)0.1 W✓ OK (≤3%)
400 mm²570 A445 A0.01 V (0.03%)48.0 V0.02 V (0.05%)0.1 W✓ OK (≤3%)

FAQ — 5 Amp Cable Size at 25 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 5A at 25 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 4 mm² copper cable for 5A over 25m at 48V (voltage drop: 1.34V or 2.79%).

What is the power capacity of 5A at 48V?

At unity power factor, 5A at 48V supports 0.24 kW with a standard 6A circuit breaker.