5 Amp Cable Size at 40 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 5 A over 40 m (131.2 ft).

Copper Cable (≤3% Drop)6 mm²Drop: 1.43V (2.97%)
Aluminum Cable (≤3% Drop)10 mm²Drop: 1.41V (2.94%)
Voltage at Load46.6 VLine Loss: 7.1 W
Max Power & Breaker0.24 kW6A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 5A at 40m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A5.71 V (11.89%)42.3 V9.41 V (19.61%)28.5 WDrop High
2.5 mm²24 A18 A3.42 V (7.13%)44.6 V5.65 V (11.77%)17.1 WDrop High
4 mm²32 A25 A2.14 V (4.46%)45.9 V3.53 V (7.35%)10.7 W~ ≤5%
6 mm²41 A32 A1.43 V (2.97%)46.6 V2.35 V (4.9%)7.1 W✓ OK (≤3%)
10 mm²57 A44 A0.86 V (1.78%)47.1 V1.41 V (2.94%)4.3 W✓ OK (≤3%)
16 mm²76 A59 A0.54 V (1.11%)47.5 V0.88 V (1.84%)2.7 W✓ OK (≤3%)
25 mm²101 A78 A0.34 V (0.71%)47.7 V0.56 V (1.18%)1.7 W✓ OK (≤3%)
35 mm²125 A97 A0.24 V (0.51%)47.8 V0.4 V (0.84%)1.2 W✓ OK (≤3%)
50 mm²151 A118 A0.17 V (0.36%)47.8 V0.28 V (0.59%)0.9 W✓ OK (≤3%)
70 mm²192 A150 A0.12 V (0.25%)47.9 V0.2 V (0.42%)0.6 W✓ OK (≤3%)
95 mm²232 A181 A0.09 V (0.19%)47.9 V0.15 V (0.31%)0.5 W✓ OK (≤3%)
120 mm²269 A210 A0.07 V (0.15%)47.9 V0.12 V (0.25%)0.4 W✓ OK (≤3%)
150 mm²309 A241 A0.06 V (0.12%)47.9 V0.09 V (0.2%)0.3 W✓ OK (≤3%)
185 mm²353 A275 A0.05 V (0.1%)48.0 V0.08 V (0.16%)0.2 W✓ OK (≤3%)
240 mm²415 A324 A0.04 V (0.07%)48.0 V0.06 V (0.12%)0.2 W✓ OK (≤3%)
300 mm²477 A372 A0.03 V (0.06%)48.0 V0.05 V (0.1%)0.1 W✓ OK (≤3%)
400 mm²570 A445 A0.02 V (0.04%)48.0 V0.04 V (0.07%)0.1 W✓ OK (≤3%)

FAQ — 5 Amp Cable Size at 40 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 5A at 40 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 6 mm² copper cable for 5A over 40m at 48V (voltage drop: 1.43V or 2.97%).

What is the power capacity of 5A at 48V?

At unity power factor, 5A at 48V supports 0.24 kW with a standard 6A circuit breaker.