5 Amp Cable Size at 35 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 5 A over 35 m (114.8 ft).

Copper Cable (≤3% Drop)6 mm²Drop: 1.25V (2.6%)
Aluminum Cable (≤3% Drop)10 mm²Drop: 1.24V (2.57%)
Voltage at Load46.8 VLine Loss: 6.2 W
Max Power & Breaker0.24 kW6A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 5A at 35m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A4.99 V (10.4%)43.0 V8.24 V (17.16%)25.0 WDrop High
2.5 mm²24 A18 A3.0 V (6.24%)45.0 V4.94 V (10.3%)15.0 WDrop High
4 mm²32 A25 A1.87 V (3.9%)46.1 V3.09 V (6.43%)9.4 W~ ≤5%
6 mm²41 A32 A1.25 V (2.6%)46.8 V2.06 V (4.29%)6.2 W✓ OK (≤3%)
10 mm²57 A44 A0.75 V (1.56%)47.3 V1.24 V (2.57%)3.7 W✓ OK (≤3%)
16 mm²76 A59 A0.47 V (0.98%)47.5 V0.77 V (1.61%)2.3 W✓ OK (≤3%)
25 mm²101 A78 A0.3 V (0.62%)47.7 V0.49 V (1.03%)1.5 W✓ OK (≤3%)
35 mm²125 A97 A0.21 V (0.45%)47.8 V0.35 V (0.74%)1.1 W✓ OK (≤3%)
50 mm²151 A118 A0.15 V (0.31%)47.9 V0.25 V (0.51%)0.7 W✓ OK (≤3%)
70 mm²192 A150 A0.11 V (0.22%)47.9 V0.18 V (0.37%)0.5 W✓ OK (≤3%)
95 mm²232 A181 A0.08 V (0.16%)47.9 V0.13 V (0.27%)0.4 W✓ OK (≤3%)
120 mm²269 A210 A0.06 V (0.13%)47.9 V0.1 V (0.21%)0.3 W✓ OK (≤3%)
150 mm²309 A241 A0.05 V (0.1%)48.0 V0.08 V (0.17%)0.2 W✓ OK (≤3%)
185 mm²353 A275 A0.04 V (0.08%)48.0 V0.07 V (0.14%)0.2 W✓ OK (≤3%)
240 mm²415 A324 A0.03 V (0.07%)48.0 V0.05 V (0.11%)0.2 W✓ OK (≤3%)
300 mm²477 A372 A0.02 V (0.05%)48.0 V0.04 V (0.09%)0.1 W✓ OK (≤3%)
400 mm²570 A445 A0.02 V (0.04%)48.0 V0.03 V (0.06%)0.1 W✓ OK (≤3%)

FAQ — 5 Amp Cable Size at 35 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 5A at 35 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 6 mm² copper cable for 5A over 35m at 48V (voltage drop: 1.25V or 2.6%).

What is the power capacity of 5A at 48V?

At unity power factor, 5A at 48V supports 0.24 kW with a standard 6A circuit breaker.