5 Amp Cable Size at 50 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 5 A over 50 m (164.0 ft).

Copper Cable (≤3% Drop)10 mm²Drop: 1.07V (2.23%)
Aluminum Cable (≤3% Drop)16 mm²Drop: 1.1V (2.3%)
Voltage at Load46.9 VLine Loss: 5.3 W
Max Power & Breaker0.24 kW6A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 5A at 50m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A7.13 V (14.86%)40.9 V11.77 V (24.51%)35.7 WDrop High
2.5 mm²24 A18 A4.28 V (8.92%)43.7 V7.06 V (14.71%)21.4 WDrop High
4 mm²32 A25 A2.67 V (5.57%)45.3 V4.41 V (9.19%)13.4 WDrop High
6 mm²41 A32 A1.78 V (3.72%)46.2 V2.94 V (6.13%)8.9 W~ ≤5%
10 mm²57 A44 A1.07 V (2.23%)46.9 V1.76 V (3.68%)5.3 W✓ OK (≤3%)
16 mm²76 A59 A0.67 V (1.39%)47.3 V1.1 V (2.3%)3.3 W✓ OK (≤3%)
25 mm²101 A78 A0.43 V (0.89%)47.6 V0.71 V (1.47%)2.1 W✓ OK (≤3%)
35 mm²125 A97 A0.31 V (0.64%)47.7 V0.5 V (1.05%)1.5 W✓ OK (≤3%)
50 mm²151 A118 A0.21 V (0.45%)47.8 V0.35 V (0.74%)1.1 W✓ OK (≤3%)
70 mm²192 A150 A0.15 V (0.32%)47.8 V0.25 V (0.53%)0.8 W✓ OK (≤3%)
95 mm²232 A181 A0.11 V (0.23%)47.9 V0.19 V (0.39%)0.6 W✓ OK (≤3%)
120 mm²269 A210 A0.09 V (0.19%)47.9 V0.15 V (0.31%)0.4 W✓ OK (≤3%)
150 mm²309 A241 A0.07 V (0.15%)47.9 V0.12 V (0.25%)0.4 W✓ OK (≤3%)
185 mm²353 A275 A0.06 V (0.12%)47.9 V0.1 V (0.2%)0.3 W✓ OK (≤3%)
240 mm²415 A324 A0.04 V (0.09%)48.0 V0.07 V (0.15%)0.2 W✓ OK (≤3%)
300 mm²477 A372 A0.04 V (0.07%)48.0 V0.06 V (0.12%)0.2 W✓ OK (≤3%)
400 mm²570 A445 A0.03 V (0.06%)48.0 V0.04 V (0.09%)0.1 W✓ OK (≤3%)

FAQ — 5 Amp Cable Size at 50 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 5A at 50 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 10 mm² copper cable for 5A over 50m at 48V (voltage drop: 1.07V or 2.23%).

What is the power capacity of 5A at 48V?

At unity power factor, 5A at 48V supports 0.24 kW with a standard 6A circuit breaker.