125 Amp Cable Size at 40 Meters (690V Three-Phase (Wind / Heavy Industrial))
IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 125 A over 40 m (131.2 ft).
Copper Cable (≤3% Drop)35 mm²Drop: 5.3V (0.77%)
Aluminum Cable (≤3% Drop)70 mm²Drop: 4.37V (0.63%)
Voltage at Load684.7 VLine Loss: 1146.4 W
Max Power & Breaker149.39 kW125A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 125A at 40m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 123.55 V (17.91%) | 566.4 V | 203.8 V (29.54%) | 26750.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 74.13 V (10.74%) | 615.9 V | 122.28 V (17.72%) | 16050.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 46.33 V (6.71%) | 643.7 V | 76.43 V (11.08%) | 10031.2 W | Drop High |
| 6 mm² | 41 A | 32 A | 30.89 V (4.48%) | 659.1 V | 50.95 V (7.38%) | 6687.5 W | Drop High |
| 10 mm² | 57 A | 44 A | 18.53 V (2.69%) | 671.5 V | 30.57 V (4.43%) | 4012.5 W | Drop High |
| 16 mm² | 76 A | 59 A | 11.58 V (1.68%) | 678.4 V | 19.11 V (2.77%) | 2507.8 W | Drop High |
| 25 mm² | 101 A | 78 A | 7.41 V (1.07%) | 682.6 V | 12.23 V (1.77%) | 1605.0 W | Drop High |
| 35 mm² | 125 A | 97 A | 5.3 V (0.77%) | 684.7 V | 8.73 V (1.27%) | 1146.4 W | ✓ OK (≤3%) |
| 50 mm² | 151 A | 118 A | 3.71 V (0.54%) | 686.3 V | 6.11 V (0.89%) | 802.5 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 2.65 V (0.38%) | 687.4 V | 4.37 V (0.63%) | 573.2 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 1.95 V (0.28%) | 688.0 V | 3.22 V (0.47%) | 422.4 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 1.54 V (0.22%) | 688.5 V | 2.55 V (0.37%) | 334.4 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 1.24 V (0.18%) | 688.8 V | 2.04 V (0.3%) | 267.5 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 1.0 V (0.15%) | 689.0 V | 1.65 V (0.24%) | 216.9 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.77 V (0.11%) | 689.2 V | 1.27 V (0.18%) | 167.2 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.62 V (0.09%) | 689.4 V | 1.02 V (0.15%) | 133.8 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.46 V (0.07%) | 689.5 V | 0.76 V (0.11%) | 100.3 W | ✓ OK (≤3%) |
FAQ — 125 Amp Cable Size at 40 Meters (690V Three-Phase (Wind / Heavy Industrial))
What mm² cable size is required for 125A at 40 meters (690V)?
According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 35 mm² copper cable for 125A over 40m at 690V (voltage drop: 5.3V or 0.77%).
What is the power capacity of 125A at 690V?
At unity power factor, 125A at 690V supports 149.39 kW with a standard 125A circuit breaker.
Related Lengths & Currents (690V)
125A · 5m (690V)125A · 10m (690V)125A · 15m (690V)125A · 20m (690V)125A · 25m (690V)125A · 30m (690V)125A · 35m (690V)125A · 45m (690V)125A · 50m (690V)125A · 60m (690V)125A · 70m (690V)10A · 40m (690V)16A · 40m (690V)20A · 40m (690V)25A · 40m (690V)32A · 40m (690V)40A · 40m (690V)50A · 40m (690V)63A · 40m (690V)80A · 40m (690V)100A · 40m (690V)160A · 40m (690V)200A · 40m (690V)