500 Amp Cable Size at 250 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 500 A over 250 m (820.2 ft).

Copper Cable (≤3% Drop)400 mm²Drop: 11.58V (2.79%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 19.11V (4.6%)
Voltage at Load403.4 VLine Loss: 10031.2 W
Max Power & Breaker359.4 kW500A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 500A at 250m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A3088.82 V (744.29%)0.0 V5095.12 V (1227.74%)2675000.0 WDrop High
2.5 mm²24 A18 A1853.29 V (446.58%)0.0 V3057.07 V (736.64%)1605000.0 WDrop High
4 mm²32 A25 A1158.31 V (279.11%)0.0 V1910.67 V (460.4%)1003125.0 WDrop High
6 mm²41 A32 A772.21 V (186.07%)0.0 V1273.78 V (306.93%)668750.0 WDrop High
10 mm²57 A44 A463.32 V (111.64%)0.0 V764.27 V (184.16%)401250.0 WDrop High
16 mm²76 A59 A289.58 V (69.78%)125.4 V477.67 V (115.1%)250781.2 WDrop High
25 mm²101 A78 A185.33 V (44.66%)229.7 V305.71 V (73.66%)160500.0 WDrop High
35 mm²125 A97 A132.38 V (31.9%)282.6 V218.36 V (52.62%)114642.9 WDrop High
50 mm²151 A118 A92.66 V (22.33%)322.3 V152.85 V (36.83%)80250.0 WDrop High
70 mm²192 A150 A66.19 V (15.95%)348.8 V109.18 V (26.31%)57321.4 WDrop High
95 mm²232 A181 A48.77 V (11.75%)366.2 V80.45 V (19.39%)42236.8 WDrop High
120 mm²269 A210 A38.61 V (9.3%)376.4 V63.69 V (15.35%)33437.5 WDrop High
150 mm²309 A241 A30.89 V (7.44%)384.1 V50.95 V (12.28%)26750.0 WDrop High
185 mm²353 A275 A25.04 V (6.03%)390.0 V41.31 V (9.95%)21689.2 WDrop High
240 mm²415 A324 A19.31 V (4.65%)395.7 V31.84 V (7.67%)16718.8 WDrop High
300 mm²477 A372 A15.44 V (3.72%)399.6 V25.48 V (6.14%)13375.0 WDrop High
400 mm²570 A445 A11.58 V (2.79%)403.4 V19.11 V (4.6%)10031.2 W✓ OK (≤3%)

FAQ — 500 Amp Cable Size at 250 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 500A at 250 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 400 mm² copper cable for 500A over 250m at 415V (voltage drop: 11.58V or 2.79%).

What is the power capacity of 500A at 415V?

At unity power factor, 500A at 415V supports 359.4 kW with a standard 500A circuit breaker.