550 Amp Cable Size at 100 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 550 A over 100 m (328.1 ft).

Copper Cable (≤3% Drop)5× 400 mm²Drop: 1.18V (2.45%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 9.71V (20.22%)
Voltage at Load46.8 VLine Loss: 647.3 W
Max Power & Breaker26.4 kW600A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 550A at 100m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1569.33 V (3269.44%)0.0 V2588.67 V (5393.06%)863133.3 WDrop High
2.5 mm²24 A18 A941.6 V (1961.67%)0.0 V1553.2 V (3235.83%)517880.0 WDrop High
4 mm²32 A25 A588.5 V (1226.04%)0.0 V970.75 V (2022.4%)323675.0 WDrop High
6 mm²41 A32 A392.33 V (817.36%)0.0 V647.17 V (1348.26%)215783.3 WDrop High
10 mm²57 A44 A235.4 V (490.42%)0.0 V388.3 V (808.96%)129470.0 WDrop High
16 mm²76 A59 A147.12 V (306.51%)0.0 V242.69 V (505.6%)80918.7 WDrop High
25 mm²101 A78 A94.16 V (196.17%)0.0 V155.32 V (323.58%)51788.0 WDrop High
35 mm²125 A97 A67.26 V (140.12%)0.0 V110.94 V (231.13%)36991.4 WDrop High
50 mm²151 A118 A47.08 V (98.08%)0.9 V77.66 V (161.79%)25894.0 WDrop High
70 mm²192 A150 A33.63 V (70.06%)14.4 V55.47 V (115.57%)18495.7 WDrop High
95 mm²232 A181 A24.78 V (51.62%)23.2 V40.87 V (85.15%)13628.4 WDrop High
120 mm²269 A210 A19.62 V (40.87%)28.4 V32.36 V (67.41%)10789.2 WDrop High
150 mm²309 A241 A15.69 V (32.69%)32.3 V25.89 V (53.93%)8631.3 WDrop High
185 mm²353 A275 A12.72 V (26.51%)35.3 V20.99 V (43.73%)6998.4 WDrop High
240 mm²415 A324 A9.81 V (20.43%)38.2 V16.18 V (33.71%)5394.6 WDrop High
300 mm²477 A372 A7.85 V (16.35%)40.2 V12.94 V (26.97%)4315.7 WDrop High
400 mm²570 A445 A5.88 V (12.26%)42.1 V9.71 V (20.22%)3236.7 WDrop High

FAQ — 550 Amp Cable Size at 100 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 550A at 100 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 5× 400 mm² copper cable for 550A over 100m at 48V (voltage drop: 1.18V or 2.45%).

What is the power capacity of 550A at 48V?

At unity power factor, 550A at 48V supports 26.4 kW with a standard 600A circuit breaker.