⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

550 Amp Cable Size at 350 Meters (400V Three-Phase (IEC European Grid))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 550 A over 350 m (1148.3 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 8.92V (2.23%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 29.42V (7.36%)
Voltage at Load391.1 VLine Loss: 8496.5 W
Max Power & Breaker381.05 kW600A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 550A at 350m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A4756.79 V (1189.2%)0.0 V7846.48 V (1961.62%)4531450.0 WDrop High
2.5 mm²24 A18 A2854.07 V (713.52%)0.0 V4707.89 V (1176.97%)2718870.0 WDrop High
4 mm²32 A25 A1783.8 V (445.95%)0.0 V2942.43 V (735.61%)1699293.7 WDrop High
6 mm²41 A32 A1189.2 V (297.3%)0.0 V1961.62 V (490.4%)1132862.5 WDrop High
10 mm²57 A44 A713.52 V (178.38%)0.0 V1176.97 V (294.24%)679717.5 WDrop High
16 mm²76 A59 A445.95 V (111.49%)0.0 V735.61 V (183.9%)424823.4 WDrop High
25 mm²101 A78 A285.41 V (71.35%)114.6 V470.79 V (117.7%)271887.0 WDrop High
35 mm²125 A97 A203.86 V (50.97%)196.1 V336.28 V (84.07%)194205.0 WDrop High
50 mm²151 A118 A142.7 V (35.68%)257.3 V235.39 V (58.85%)135943.5 WDrop High
70 mm²192 A150 A101.93 V (25.48%)298.1 V168.14 V (42.03%)97102.5 WDrop High
95 mm²232 A181 A75.11 V (18.78%)324.9 V123.89 V (30.97%)71549.2 WDrop High
120 mm²269 A210 A59.46 V (14.86%)340.5 V98.08 V (24.52%)56643.1 WDrop High
150 mm²309 A241 A47.57 V (11.89%)352.4 V78.46 V (19.62%)45314.5 WDrop High
185 mm²353 A275 A38.57 V (9.64%)361.4 V63.62 V (15.91%)36741.5 WDrop High
240 mm²415 A324 A29.73 V (7.43%)370.3 V49.04 V (12.26%)28321.6 WDrop High
300 mm²477 A372 A23.78 V (5.95%)376.2 V39.23 V (9.81%)22657.2 WDrop High
400 mm²570 A445 A17.84 V (4.46%)382.2 V29.42 V (7.36%)16992.9 W~ ≤5%

FAQ — 550 Amp Cable Size at 350 Meters (400V Three-Phase (IEC European Grid))

What mm² cable size is required for 550A at 350 meters (400V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 550A over 350m at 400V (voltage drop: 8.92V or 2.23%).

What is the power capacity of 550A at 400V?

At unity power factor, 550A at 400V supports 381.05 kW with a standard 600A circuit breaker.