60 Amp Cable Size at 350 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 60 A over 350 m (1148.3 ft).

Copper Cable (≤3% Drop)70 mm²Drop: 11.12V (2.68%)
Aluminum Cable (≤3% Drop)120 mm²Drop: 10.7V (2.58%)
Voltage at Load403.9 VLine Loss: 1155.6 W
Max Power & Breaker43.13 kW60A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 60A at 350m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A518.92 V (125.04%)0.0 V855.98 V (206.26%)53928.0 WDrop High
2.5 mm²24 A18 A311.35 V (75.02%)103.6 V513.59 V (123.76%)32356.8 WDrop High
4 mm²32 A25 A194.6 V (46.89%)220.4 V320.99 V (77.35%)20223.0 WDrop High
6 mm²41 A32 A129.73 V (31.26%)285.3 V213.99 V (51.57%)13482.0 WDrop High
10 mm²57 A44 A77.84 V (18.76%)337.2 V128.4 V (30.94%)8089.2 WDrop High
16 mm²76 A59 A48.65 V (11.72%)366.4 V80.25 V (19.34%)5055.7 WDrop High
25 mm²101 A78 A31.14 V (7.5%)383.9 V51.36 V (12.38%)3235.7 WDrop High
35 mm²125 A97 A22.24 V (5.36%)392.8 V36.68 V (8.84%)2311.2 WDrop High
50 mm²151 A118 A15.57 V (3.75%)399.4 V25.68 V (6.19%)1617.8 W~ ≤5%
70 mm²192 A150 A11.12 V (2.68%)403.9 V18.34 V (4.42%)1155.6 W✓ OK (≤3%)
95 mm²232 A181 A8.19 V (1.97%)406.8 V13.52 V (3.26%)851.5 W✓ OK (≤3%)
120 mm²269 A210 A6.49 V (1.56%)408.5 V10.7 V (2.58%)674.1 W✓ OK (≤3%)
150 mm²309 A241 A5.19 V (1.25%)409.8 V8.56 V (2.06%)539.3 W✓ OK (≤3%)
185 mm²353 A275 A4.21 V (1.01%)410.8 V6.94 V (1.67%)437.3 W✓ OK (≤3%)
240 mm²415 A324 A3.24 V (0.78%)411.8 V5.35 V (1.29%)337.0 W✓ OK (≤3%)
300 mm²477 A372 A2.59 V (0.63%)412.4 V4.28 V (1.03%)269.6 W✓ OK (≤3%)
400 mm²570 A445 A1.95 V (0.47%)413.1 V3.21 V (0.77%)202.2 W✓ OK (≤3%)

FAQ — 60 Amp Cable Size at 350 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 60A at 350 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 70 mm² copper cable for 60A over 350m at 415V (voltage drop: 11.12V or 2.68%).

What is the power capacity of 60A at 415V?

At unity power factor, 60A at 415V supports 43.13 kW with a standard 60A circuit breaker.